# DEVICE:URL:REPORT: https://github.com/networkupstools/nut/issues/117 ambient.temperature.high: 137 ambient.temperature.low: 34 device.mfr: Eaton device.model: POWERWARE UPS 700i device.serial: device.type: ups driver.name: bcmxcp_usb driver.parameter.pollinterval: 2 driver.parameter.port: foo driver.parameter.shutdown_delay: 15 driver.version: 2.6.3 driver.version.internal: 0.25 input.frequency.high: 55 input.frequency.low: 45 input.frequency.nominal: 50 input.transfer.high: 6144 input.voltage.nominal: 240 output.phases: 1 output.voltage.nominal: 240 ups.beeper.status: disabled #BAD: 'ups.beeper.status' appears to not work: the beeper still goes on even though it displays as 'disabled'. ups.firmware: Cont:00.80 Inve:00.60 ups.mfr: Eaton ups.model: POWERWARE UPS 700i ups.power.nominal: 700 ups.serial: ups.status: OL #CMD:shutdown.return #CMD:shutdown.stayoff # shutdown.stayoff:COMMENT: # 'shutdown.stayoff' powers off immediately (no shutdown delay), and then powers on again when line power is available. # shutdown.stayoff:EOC #CMD:test.battery.start #BAD # test.battery.start:COMMENT: # 'test.battery.start' does not have any noticeable effect: the device does not report any battery information so it's impossible to know if it actually does a test and what the results are (but most likely it just does nothing). # test.battery.start:EOC