# DEVICE:URL:REPORT: https://github.com/networkupstools/nut/pull/584 # DEVICE:COMMENT: # Shutdown sequence is a work in progress, but without `battery.charge` # there is no low battery. And the jumping battery voltage levels when # the charge gets lower aren't helping either. # DEVICE:EOC # upsc output: battery.charge: 100 battery.voltage: 13.90 battery.voltage.nominal: 12 device.mfr: Tripp Lite device.model: SMX500RT1U device.type: ups driver.name: tripplite_usb driver.parameter.pollinterval: 2 driver.parameter.port: auto driver.parameter.synchronous: no driver.version: 2.7.4.1 driver.version.internal: 0.30 input.voltage: 234 input.voltage.maximum: 239 input.voltage.minimum: 229 input.voltage.nominal: 120 outlet.1.desc: Load 1 outlet.1.id: 1 outlet.1.switch: 1 outlet.1.switchable: 1 outlet.2.desc: Load 2 outlet.2.id: 2 outlet.2.switchable: 0 ups.debug.D: 00 ea 00 8b 0d 00 00 '.......' ups.debug.L: 10 00 00 07 58 58 0d '....XX.' ups.debug.load_banks: 1 ups.debug.M: 00 e5 00 ef 0d 00 00 '.......' ups.debug.P: 30 30 35 30 30 58 0d '00500X.' ups.debug.S: 01 04 00 00 64 00 0d '....d..' ups.debug.T: 29 00 01 f3 00 58 0d '.....X.' ups.debug.V: 06 00 0c 01 58 58 0d '....XX.' ups.delay.shutdown: 64 ups.firmware: F334403 ups.firmware.aux: protocol 3005 ups.id: 0 ups.mfr: Tripp Lite ups.model: SMX500RT1U ups.power.nominal: 500 ups.productid: 0001 ups.status: OL ups.temperature: 0 ups.vendorid: 09ae # DEVICE:COMMENT-BLOCK:FIXME:UPSRW: # [outlet.1.switch] # Outlet switch control # Type: STRING # Maximum length: 3 # Value: 1 # # [ups.delay.shutdown] # Interval to wait after shutdown with delay command (seconds) # Type: STRING # Maximum length: 3 # Value: 64 # # [ups.id] # UPS system identifier # Type: STRING # Maximum length: 5 # Value: 0 # DEVICE:EOC