NAME
failover - UPS Failover Driver
SYNOPSIS
failover -h
failover -a UPS_NAME [OPTIONS]
Note
|
This man page only documents the specific features of the failover driver. For information about the core driver, see nutupsdrv(8). |
DESCRIPTION
The failover
driver acts as a smart proxy for multiple "real" UPS drivers. It
connects to and monitors these underlying UPS drivers through their local UNIX
sockets (or Windows named pipes), continuously evaluating health and suitability
for "primary" duty according to a set of user configurable rules and priorities.
At any given time, failover
designates one UPS driver as the primary, and
presents its commands, variables and status to the outside world as if it were
directly talking to that UPS. From the perspective of the clients (such as
upsmon(8) or upsc(8)), the failover
driver behaves like any
single UPS, abstracting away the underlying redundancy, and allowing for
seamless transitioning between all monitored UPS drivers and their datasets.
The driver dynamically promotes or demotes the primary UPS driver based on:
-
Socket availability and communication status
-
Data freshness and UPS online/offline indicators
-
User-defined status filters (e.g., presence or absence of
OL
,LB
, …) -
Administrative override via control commands (
force.primary
,force.ignore
)
If the current primary becomes unavailable or no longer meets the criteria, the driver automatically fails over to a more suitable driver. During transitions, it ensures that any data is switched out instantly, without the upsd(8) considering it as stale or the clients acting on any previously degraded status.
When no suitable primary is available, a configurable fallback state is entered:
-
Keep last primary and declare the data as stale
-
Raise
ALARM
and declare the data as stale -
Raise
ALARM
and set forced shutdown (FSD
)
Different communication media can be used to connect to individual UPS drivers
(e.g., USB, Serial, Ethernet). failover
communicates directly at the socket
level and therefore does not rely on upsd(8) being active.
EXTRA ARGUMENTS
This driver supports the following settings:
- port=drivername-devicename,drivername2-devicename2,…
-
Required. Specifies the local sockets (or Windows named pipes) of the underlying UPS drivers to be tracked. Entries must either be a path or follow the format
drivername-devicename
, as used by NUT’s internal socket naming convention (e.g.usbhid-ups-myups
). Multiple entries are comma-separated with no spaces. - inittime=seconds
-
Optional. Sets a grace period after driver startup during which the absence of a primary is tolerated. This allows time for underlying drivers to initialize. For networked connections or drivers that require "lock-picking" their communication protocol, consider increasing this value to accommodate potential longer delays. Defaults to 30 seconds.
- deadtime=seconds
-
Optional. Sets a grace period in seconds after which a non-responsive UPS driver is considered dead. Defaults to 30 seconds.
- relogtime=seconds
-
Optional. Time interval in which repeated connection failure logs are emitted for a UPS, reducing log spam during unstable conditions. Defaults to 5 seconds.
- noprimarytime=seconds
-
Optional. Duration to wait without a suitable primary UPS driver before entering the configured fallback mode (
fsdmode
). Defaults to 15 seconds. - maxconnfails=count
-
Optional. Number of consecutive connection failures allowed per UPS driver before entering into the cooldown period (
coolofftime
). Defaults to 5. - coolofftime=seconds
-
Optional. Cooldown period during which the driver pauses reconnect attempts after exceeding
maxconnfails
. Defaults to 15 seconds. - fsdmode=0|1|2
-
Optional. Defines the behavior when no suitable primary UPS driver is found after
noprimarytime
has elapsed. Defaults to 0.-
0
: Do not demote the last primary, but mark its data as stale. This is similar to how a regular UPS driver would behave when it loses its connection to the target UPS device. upsmon(8) will act on the last known (online or not) status, and decide itself whether that UPS should be considered critical. -
1
: Demote the primary, raiseALARM
, and mark the data as stale after an additional few seconds have elapsed (ensuring full propagation). This will cause upsmon(8) to detect that a device previously in an alarm state has lost its connection, consider the UPS driver critical, and possibly trigger a forced shutdown (FSD
) due to depletion ofMINSUPPLIES
. -
2
: Demote the primary, raiseALARM
, and immediately setFSD
. This will setFSD
from the driver side and preempt upsmon(8) from raising it itself. This mode is for setups where immediate shutdown is warranted, regardless of anything else, and gettingFSD
out to the clients as fast as just possible.
-
- checkruntime=0|1|2|3
-
Optional. Controls how
battery.runtime
values are used to break ties between non-fully-online UPS devices at priority 3 or lower. Has no effect on initial priority selection or whenstrictfiltering
is enabled. Defaults to 1.-
0
: Disabled. No runtime comparison is done. The first candidate with the best priority is selected according to the order of the port argument. -
1
: Comparebattery.runtime
. The UPS with the higher value is preferred. If the value is missing or invalid, the UPS cannot win the tie-break. -
2
: Comparebattery.runtime.low
. The UPS with the higher value is preferred. If the value is missing or invalid, the UPS cannot win the tie-break. -
3
: Compare both variables strictly. The UPS is preferred only if it has both a higherbattery.runtime
andbattery.runtime.low
value. If either is missing or invalid, the UPS cannot win the tie-break.
-
- strictfiltering=0|1
-
Optional. If set to 1, only UPS drivers matching the configured status filters are considered for promotion to primary. If set to 0, the hard-coded default logic is also considered when no status filters match (read more about this in the section
PRIORITIES
). Defaults to 0. - status_have_any=OL,CHRG,…
-
Optional. If any of these comma-separated tokens are present in a UPS driver’s
ups.status
, it passes this status filtering criteria. Defaults to unset. - status_have_all=OL,CHRG,…
-
Optional. All listed comma-separated tokens must be present in
ups.status
for the UPS driver to pass this status filtering criteria. Defaults to unset. - status_nothave_any=OB,OFF,…
-
Optional. If any of these comma-separated tokens are present in
ups.status
, the UPS driver does not pass this status filtering criteria. Defaults to unset. - status_nothave_all=OB,LB,…
-
Optional. If all of these comma-separated tokens are present in
ups.status
, the UPS driver does not pass this status filtering criteria. Defaults to unset.
Note
|
The status_* arguments are primarily intended to adjust the weighting of
UPS drivers, allowing some to be prioritized over others based on their status.
For example, a driver reporting OL might be preferred over one reporting
ALARM OL . While strictfiltering can be enabled, status filters are most
effective when used in combination with the default set of connectivity-based
PRIORITIES . For more details, see the respective section further below. |
IMPLEMENTATION
The port argument in the ups.conf(5) should reference the local driver sockets (or Windows named pipes) that the "real" UPS drivers are using. A basic default setup with multiple drivers could look like this:
[realups]
driver = usbhid-ups
port = auto
[realups2]
driver = usbhid-ups
port = auto
[failover]
driver = failover
port = usbhid-ups-realups,usbhid-ups-realups2
Any upsmon(8) clients would be set to monitor the failover
UPS.
The driver fully supports setting variables and performing instant commands on
the currently elected primary UPS driver, which are proxied and with end-to-end
tracking also being possible (upscmd(1) and upsrw(1) -w
). You
may notice some variables and commands will be prefixed with upstream.
, this
is to clearly separate the upstream commands from those of failover
itself.
For your convenience, additional administrative commands are exposed to directly influence and override the primary election process, e.g. for maintenance:
-
<socketname>.force.ignore [seconds]
prevents the specified UPS driver from being selected as primary for the given duration, or permanently if a negative value is used. A value of0
resets this override and re-enables selection. -
<socketname>.force.primary [seconds]
forces the specified UPS driver to be treated with the highest priority for the given duration, or permanently if a negative value is used. A value of0
resets this override.
Calling either command without an argument has the same effect as passing 0
,
but only for that specific override - it does not affect the other.
PRIORITIES
As outlined above, primaries are dynamically elected based on their current state and according to a strict set of user influenceable priorities, which are:
-
0
(highest): UPS driver was forced to the top by administrative command. -
1
: UPS driver has passed the user-defined status filters. -
2
: UPS driver has fresh data and is online (in statusOL
). -
3
: UPS driver has fresh data, but may not be fully online. -
4
(lowest): UPS driver is alive, but may not have fresh data.
The UPS driver with the highest calculated priority is chosen as primary, ties
are resolved through order of the socket names given within the port
argument.
For the user-defined status filters, the following internal order is respected:
-
status_nothave_any
(first) -
status_have_all
-
status_nothave_all
-
status_have_any
(last)
If strictfiltering
is enabled, priorities 2 to 4 are not applicable.
If no user-defined status filters are set, the priority 1 is not applicable.
Note
|
The base requirement for any election is the UPS socket being connectable and the UPS driver having published at least one full batch of data during its lifetime. UPS driver not fulfilling that requirement are always disqualified. |
RATIONALE
In complex power environments, presenting a single, consistent source of UPS
information to upsmon(8) is sometimes preferable to monitoring multiple
independent drivers directly. The failover
driver serves as a bridge, allowing
upsmon(8) to make decisions based on the most suitable available data,
without having to interpret conflicting inputs or degraded sources.
Originally designed for use cases such as dual-PSU systems or redundant
communication paths to a single UPS, failover
also supports more advanced
setups - for example, when multiple UPSes feed a shared downstream load (via
STS/ATS switches), or when drivers vary in reliability. In these cases, the
driver can be combined with external logic or scripting to dynamically adjust
primary selection and facilitate graceful degradation. Such setups may also
benefit from further integration with the clone
family of drivers, such as
clone(8) or clone-outlet(8), for greater granularity and
monitoring control down to the outlet level.
Additionally, in more niche scenarios, some third-party NUT integrations or
graphical interfaces may be limited to monitoring a single UPS device. In such
cases, failover
can help by exposing only the most relevant or
highest-priority data source, allowing those tools to operate within their
constraints without missing critical information.
Ultimately, this driver enables more nuanced power monitoring and control than binary online/offline logic alone, allowing administrators to respond to degraded conditions early - before they escalate into critical events or require upsmon(8) to take action.
LIMITATIONS
When using failover
for redundancy between multiple UPS drivers connected to
the same underlying UPS device, data is not multiplexed between the drivers. As
a result, some data points may be available in some drivers but not in others.
For checkruntime
considerations, the unit of both battery.runtime
and
battery.runtime.low
is assumed to be seconds. UPS drivers that report
these values using different units are considered non-compliant with the NUT
variable standards and should be reported to the NUT developers as faulty.
AUTHOR
Sebastian Kuttnig <sebastian.kuttnig@gmail.com>
SEE ALSO
Internet Resources:
The NUT (Network UPS Tools) home page: https://www.networkupstools.org/