some of these data will be redundant with ups.* information during a transition period. The ups.* data will then be removed.
Name | Description | Example value |
---|---|---|
device.model | Device model | BladeUPS |
device.mfr | Device manufacturer | Eaton |
device.serial | Device serial number (opaque string) | WS9643050926 |
device.type | Device type (ups, pdu, scd, psu, ats) | ups |
device.description | Device description (opaque string) | Some ups |
device.contact | Device administrator name (opaque string) | John Doe |
device.location | Device physical location (opaque string) | 1st floor |
device.part | Device part number (opaque string) | 123456789 |
device.macaddr | Physical network address of the device | 68:b5:99:f5:89:27 |
device.uptime | Device uptime in seconds | 1782 |
Name | Description | Example value |
---|---|---|
ups.status | UPS status | |
ups.alarm | UPS alarms | OVERHEAT |
ups.time | Internal UPS clock time (opaque string) | 12:34 |
ups.date | Internal UPS clock date (opaque string) | 01-02-03 |
ups.model | UPS model | SMART-UPS 700 |
ups.mfr | UPS manufacturer | APC |
ups.mfr.date | UPS manufacturing date (opaque string) | 10/17/96 |
ups.serial | UPS serial number (opaque string) | WS9643050926 |
ups.vendorid | Vendor ID for USB devices | 0463 |
ups.productid | Product ID for USB devices | 0001 |
ups.firmware | UPS firmware (opaque string) | 50.9.D |
ups.firmware.aux | Auxiliary device firmware | 4Kx |
ups.temperature | UPS temperature (degrees C) | 042.7 |
ups.load | Load on UPS (percent) | 023.4 |
ups.load.high | Load when UPS switches to overload condition ("OVER") (percent) | 100 |
ups.id | UPS system identifier (opaque string) | Sierra |
ups.delay.start | Interval to wait before restarting the load (seconds) | 0 |
ups.delay.reboot | Interval to wait before rebooting the UPS (seconds) | 60 |
ups.delay.shutdown | Interval to wait after shutdown with delay command (seconds) | 20 |
ups.timer.start | Time before the load will be started (seconds) | 30 |
ups.timer.reboot | Time before the load will be rebooted (seconds) | 10 |
ups.timer.shutdown | Time before the load will be shutdown (seconds) | 20 |
ups.test.interval | Interval between self tests (seconds) | 1209600 (two weeks) |
ups.test.result | Results of last self test (opaque string) | Bad battery pack |
ups.test.date | Date of last self test (opaque string) | 07/17/12 |
ups.display.language | Language to use on front panel (* opaque) | E |
ups.contacts | UPS external contact sensors (* opaque) | F0 |
ups.efficiency | Efficiency of the UPS (ratio of the output current on the input current) (percent) | 95 |
ups.power | Current value of apparent power (Volt-Amps) | 500 |
ups.power.nominal | Nominal value of apparent power (Volt-Amps) | 500 |
ups.realpower | Current value of real power (Watts) | 300 |
ups.realpower.nominal | Nominal value of real power (Watts) | 300 |
ups.beeper.status | UPS beeper status (enabled, disabled or muted) | enabled |
ups.type | UPS type (* opaque) | offline |
ups.watchdog.status | UPS watchdog status (enabled or disabled) | disabled |
ups.start.auto | UPS starts when mains is (re)applied | yes |
ups.start.battery | Allow to start UPS from battery | yes |
ups.start.reboot | UPS coldstarts from battery (enabled or disabled) | yes |
ups.shutdown | Enable or disable UPS shutdown ability (poweroff) | enabled |
When present, the value of ups.start.auto has an impact on shutdown.* commands. For the sake of coherence, shutdown commands will set ups.start.auto to the right value before issuing the command. That is, shutdown.stayoff will first set ups.start.auto to no, while shutdown.return will set it to yes.
Name | Description | Example value |
---|---|---|
input.voltage | Input voltage (V) | 121.5 |
input.voltage.maximum | Maximum incoming voltage seen (V) | 130 |
input.voltage.minimum | Minimum incoming voltage seen (V) | 100 |
input.voltage.status | Status relative to the thresholds | critical-low |
input.voltage.low.warning | Low warning threshold (V) | 205 |
input.voltage.low.critical | Low critical threshold (V) | 200 |
input.voltage.high.warning | High warning threshold (V) | 230 |
input.voltage.high.critical | High critical threshold (V) | 240 |
input.voltage.nominal | Nominal input voltage (V) | 120 |
input.voltage.extended | Extended input voltage range | no |
input.transfer.delay | Delay before transfer to mains (seconds) | 60 |
input.transfer.reason | Reason for last transfer to battery (* opaque) | T |
input.transfer.low | Low voltage transfer point (V) | 91 |
input.transfer.high | High voltage transfer point (V) | 132 |
input.transfer.low.min | smallest settable low voltage transfer point (V) | 85 |
input.transfer.low.max | greatest settable low voltage transfer point (V) | 95 |
input.transfer.high.min | smallest settable high voltage transfer point (V) | 131 |
input.transfer.high.max | greatest settable high voltage transfer point (V) | 136 |
input.sensitivity | Input power sensitivity | H (high) |
input.quality | Input power quality (* opaque) | FF |
input.current | Input current (A) | 4.25 |
input.current.nominal | Nominal input current (A) | 5.0 |
input.current.status | Status relative to the thresholds | critical-high |
input.current.low.warning | Low warning threshold (A) | 4 |
input.current.low.critical | Low critical threshold (A) | 2 |
input.current.high.warning | High warning threshold (A) | 10 |
input.current.high.critical | High critical threshold (A) | 12 |
input.frequency | Input line frequency (Hz) | 60.00 |
input.frequency.nominal | Nominal input line frequency (Hz) | 60 |
input.frequency.status | Frequency status | out-of-range |
input.frequency.low | Input line frequency low (Hz) | 47 |
input.frequency.high | Input line frequency high (Hz) | 63 |
input.frequency.extended | Extended input frequency range | no |
input.transfer.boost.low | Low voltage boosting transfer point (V) | 190 |
input.transfer.boost.high | High voltage boosting transfer point (V) | 210 |
input.transfer.trim.low | Low voltage trimming transfer point (V) | 230 |
input.transfer.trim.high | High voltage trimming transfer point (V) | 240 |
input.load | Load on (ePDU) input (percent of full) | 25 |
input.realpower | Current sum value of all (ePDU) phases real power (W) | 300 |
input.power | Current sum value of all (ePDU) phases apparent power (VA) | 500 |
input.source | The current input power source | 1 |
input.source.preferred | The preferred power source | 1 |
Name | Description | Example value |
---|---|---|
output.voltage | Output voltage (V) | 120.9 |
output.voltage.nominal | Nominal output voltage (V) | 120 |
output.frequency | Output frequency (Hz) | 59.9 |
output.frequency.nominal | Nominal output frequency (Hz) | 60 |
output.current | Output current (A) | 4.25 |
output.current.nominal | Nominal output current (A) | 5.0 |
The additions for three-phase measurements would produce a very long table due to all the combinations that are possible, so these additions are broken down to their base components.
input.phases (3 for three-phase, absent or 1 for 1phase) output.phases (as for input.phases)
Any input or output is considered a valid DOMAIN.
input (should really be called input.mains, but keep this for compat) input.bypass input.servicebypass
output (should really be called output.load, but keep this for compat) output.bypass output.inverter output.servicebypass
Voltage, current, frequency, etc are considered to be a specification of the measurement.
With this notation, the old 1phase naming scheme becomes DOMAIN.SPEC
Example: input.current
When in three-phase mode, we need some way to specify the target for most measurements in more detail. We call this the CONTEXT.
With this notation, the naming scheme becomes DOMAIN.CONTEXT.SPEC when
in three-phase mode.
Example: input.L1.current
L1-L2 \ L2-L3 \ L3-L1 for voltage measurements L1-N / L2-N / L3-N /
L1 \ L2 for current and power measurements L3 / N - for current measurement
Valid with/without context (i.e. per phase or aggregated/averaged)
Name | Description |
---|---|
alarm | Alarms for phases, published in ups.alarm |
current | Current (A) |
current.maximum | Maximum seen current (A) |
current.minimum | Minimum seen current (A) |
current.status | Status relative to the thresholds |
current.low.warning | Low warning threshold (A) |
current.low.critical | Low critical threshold (A) |
current.high.warning | High warning threshold (A) |
current.high.critical | High critical threshold (A) |
current.peak | Peak current |
voltage | Voltage (V) |
voltage.nominal | Nominal voltage (V) |
voltage.maximum | Maximum seen voltage (V) |
voltage.minimum | Minimum seen voltage (V) |
voltage.status | Status relative to the thresholds |
voltage.low.warning | Low warning threshold (V) |
voltage.low.critical | Low critical threshold (V) |
voltage.high.warning | High warning threshold (V) |
voltage.high.critical | High critical threshold (V) |
power | Apparent power (VA) |
power.maximum | Maximum seen apparent power (VA) |
power.minimum | Minimum seen apparent power (VA) |
power.percent | Percentage of apparent power related to maximum load |
power.maximum.percent | Maximum seen percentage of apparent power |
power.minimum.percent | Minimum seen percentage of apparent power |
realpower | Real power (W) |
powerfactor | Power Factor (dimensionless value between 0.00 and 1.00) |
crestfactor | Crest Factor (dimensionless value greater or equal to 1) |
load | Load on (ePDU) input |
Valid without context (i.e. aggregation of all phases):
Name | Description |
---|---|
frequency | Frequency (Hz) |
frequency.nominal | Nominal frequency (Hz) |
realpower | Current value of real power (Watts) |
power | Current value of apparent power (Volt-Amps) |
Partial Three phase - Three phase example:
input.phases: 3 input.frequency: 50.0 input.L1.current: 133.0 input.bypass.L1-L2.voltage: 398.3 output.phases: 3 output.L1.power: 35700 output.powerfactor: 0.82
Partial Three phase - One phase example:
input.phases: 3 input.L2.current: 48.2 input.N.current: 3.4 input.L3-L1.voltage: 405.4 input.frequency: 50.1 output.phases: 1 output.current: 244.2 output.voltage: 120 output.frequency.nominal: 60.0
Name | Description | Example value |
---|---|---|
battery.charge | Battery charge (percent) | 100.0 |
battery.charge.low | Remaining battery level when UPS switches to LB (percent) | 20 |
battery.charge.restart | Minimum battery level for UPS restart after power-off | 20 |
battery.charge.warning | Battery level when UPS switches to "Warning" state (percent) | 50 |
battery.charger.status | Status of the battery charger (see the note below) | charging |
battery.voltage | Battery voltage (V) | 24.84 |
battery.voltage.nominal | Nominal battery voltage (V) | 024 |
battery.voltage.low | Minimum battery voltage, that triggers FSD status | 21,52 |
battery.voltage.high | Maximum battery voltage (i.e. battery.charge = 100) | 26,9 |
battery.capacity | Battery capacity (Ah) | 7.2 |
battery.current | Battery current (A) | 1.19 |
battery.current.total | Total battery current (A) | 1.19 |
battery.temperature | Battery temperature (degrees C) | 050.7 |
battery.runtime | Battery runtime (seconds) | 1080 |
battery.runtime.low | Remaining battery runtime when UPS switches to LB (seconds) | 180 |
battery.runtime.restart | Minimum battery runtime for UPS restart after power-off (seconds) | 120 |
battery.alarm.threshold | Battery alarm threshold | 0 (immediate) |
battery.date | Battery change date (opaque string) | 11/14/00 |
battery.mfr.date | Battery manufacturing date (opaque string) | 2005/04/02 |
battery.packs | Number of battery packs | 001 |
battery.packs.bad | Number of bad battery packs | 000 |
battery.type | Battery chemistry (opaque string) | PbAc |
battery.protection | Prevent deep discharge of battery | yes |
battery.energysave | Switch off when running on battery and no/low load | no |
battery.energysave.load | Switch off UPS if on battery and load level lower (percent) | 5 |
battery.energysave.delay | Delay before switch off UPS if on battery and load level low (min) | 3 |
battery.energysave.realpower | Switch off UPS if on battery and load level lower (Watts) | 10 |
NOTE: battery.charger.status replaces the historic flags CHRG and DISCHRG that were exposed through ups.status. battery.charger.status can have one of the following value:
multiple sensors can be exposed using the indexed notation. ambient.*, without index or using 0, relates to the embedded sensor. For example: ambient.temperature represent the embedded sensor temperature. Other sensors (external, communication card, …) can use indexes from 1 to n. For example: ambient.1.temperature for the first external sensor temperature.
Name | Description | Example value |
---|---|---|
ambient.n.present | Ambient sensor presence | yes |
ambient.n.temperature | Ambient temperature (degrees C) | 25.40 |
ambient.n.temperature.alarm | Temperature alarm (enabled/disabled) | enabled |
ambient.n.temperature.status | Ambient temperature status relative to the thresholds | warning-low |
ambient.n.temperature.high | Temperature threshold high (degrees C) | 60 |
ambient.n.temperature.high.warning | Temperature threshold high warning (degrees C) | 40 |
ambient.n.temperature.high.critical | Temperature threshold high critical (degrees C) | 60 |
ambient.n.temperature.low | Temperature threshold low (degrees C) | 5 |
ambient.n.temperature.low.warning | Temperature threshold low warning (degrees C) | 10 |
ambient.n.temperature.low.critical | Temperature threshold low critical (degrees C) | 5 |
ambient.n.temperature.maximum | Maximum temperature seen (degrees C) | 37.6 |
ambient.n.temperature.minimum | Minimum temperature seen (degrees C) | 18.1 |
ambient.n.humidity | Ambient relative humidity (percent) | 038.8 |
ambient.n.humidity.alarm | Relative humidity alarm (enabled/disabled) | enabled |
ambient.n.humidity.status | Ambient humidity status relative to the thresholds | warning-low |
ambient.n.humidity.high | Relative humidity threshold high (percent) | 80 |
ambient.n.humidity.high.warning | Relative humidity threshold high warning (percent) | 70 |
ambient.n.humidity.high.critical | Relative humidity threshold high critical (percent) | 80 |
ambient.n.humidity.low | Relative humidity threshold low (percent) | 10 |
ambient.n.humidity.low.warning | Relative humidity threshold low warning (percent) | 20 |
ambient.n.humidity.low.critical | Relative humidity threshold low critical (percent) | 10 |
ambient.n.humidity.maximum | Maximum relative humidity seen (percent) | 60 |
ambient.n.humidity.minimum | Minimum relative humidity seen (percent) | 13 |
ambient.n.contacts.x.status | State of the dry contact sensor x | open |
n stands for the outlet index. For more information, refer to the NUT outlets management and PDU notes chapter of the user manual. A special case is "outlet.0" which is equivalent to "outlet" (without index), and represent the whole set of outlets of the device. The most important data is "outlet.count", used to iterate over the whole set of outlets.
Name | Description | Example value |
---|---|---|
outlet.count | Total number of outlets | 12 |
outlet.n.id | Outlet system identifier (opaque string) | 1 |
outlet.n.desc | Outlet name / description (opaque string) | Main outlet |
outlet.n.groupid | Identifier of the group to which the outlet belongs to | 1 |
outlet.n.switch | Outlet switch control (on/off) | on |
outlet.n.status | Outlet switch status (on/off) | on |
outlet.n.alarm | Alarms for outlets and PDU, published in ups.alarm | outlet 1 low voltage warning |
outlet.n.switchable | Outlet switch ability (yes/no) | yes |
outlet.n.autoswitch.charge.low | Remaining battery level to power off this outlet (percent) | 80 |
outlet.n.battery.charge.low | Remaining battery level to power off this outlet (percent) | 80 |
outlet.n.delay.shutdown | Interval to wait before shutting down this outlet (seconds) | 180 |
outlet.n.delay.start | Interval to wait before restarting this outlet (seconds) | 120 |
outlet.n.timer.shutdown | Time before the outlet load will be shutdown (seconds) | 20 |
outlet.n.timer.start | Time before the outlet load will be started (seconds) | 30 |
outlet.n.current | Current (A) | 0.19 |
outlet.n.current.maximum | Maximum seen current (A) | 0.56 |
outlet.n.current.status | Current status relative to the thresholds | good |
outlet.n.current.low.warning | Low warning threshold (A) | 0.10 |
outlet.n.current.low.critical | Low critical threshold (A) | 0.05 |
outlet.n.current.high.warning | High warning threshold (A) | 0.30 |
outlet.n.current.high.critical | High critical threshold (A) | 0.40 |
outlet.n.realpower | Current value of real power (W) | 28 |
outlet.n.voltage | Voltage (V) | 247.0 |
outlet.n.voltage.status | Voltage status relative to the thresholds | good |
outlet.n.voltage.low.warning | Low warning threshold (V) | 205 |
outlet.n.voltage.low.critical | Low critical threshold (V) | 200 |
outlet.n.voltage.high.warning | High warning threshold (V) | 230 |
outlet.n.voltage.high.critical | High critical threshold (V) | 240 |
outlet.n.powerfactor | Power Factor (dimensionless, value between 0 and 1) | 0.85 |
outlet.n.crestfactor | Crest Factor (dimensionless, equal to or greater than 1) | 1.41 |
outlet.n.power | Apparent power (VA) | 46 |
This is a refinement of the outlet collection, providing grouped management for a set of outlets. The same principles and data than the outlet collection apply to outlet.group, especially for the indexing n and "outlet.group.count".
Most of the data published for outlets also apply to outlet.group, including: id, name (similar as outlet "desc"), status, current and voltage (including status, alarm and thresholds).
Some specific data to outlet groups exists:
Name | Description | Example value |
---|---|---|
outlet.group.n.type | Type of outlet group (OPAQUE) | outlet-section |
outlet.group.n.count | Number of outlets in the group | 12 |
Example:
outlet.group.1.current: 0.00 outlet.group.1.current.high.critical: 16.00 outlet.group.1.current.high.warning: 12.80 outlet.group.1.current.low.warning: 0.00 outlet.group.1.current.nominal: 16.00 outlet.group.1.current.status: good outlet.group.1.id: 1 outlet.group.1.name: Branch Circuit A outlet.group.1.status: on outlet.group.1.voltage: 244.23 outlet.group.1.voltage.high.critical: 265.00 outlet.group.1.voltage.high.warning: 255.00 outlet.group.1.voltage.low.critical: 180.00 outlet.group.1.voltage.low.warning: 190.00 outlet.group.1.voltage.status: good ... outlet.group.count: 3.00
Name | Description | Example value |
---|---|---|
driver.name | Driver name | usbhid-ups |
driver.version | Driver version (NUT release) | X.Y.Z |
driver.version.internal | Internal driver version | 1.23.45 |
driver.version.data | Version of the internal data mapping, for generic drivers | Eaton HID 1.31 |
driver.parameter.xxx | Parameter xxx (ups.conf or cmdline -x) setting | (varies) |
driver.flag.xxx | Flag xxx (ups.conf or cmdline -x) status | enabled (or absent) |
Name | Description | Example value |
---|---|---|
server.info | Server information | Network UPS Tools upsd vX.Y.Z - http://www.networkupstools.org/ |
server.version | Server version | X.Y.Z |