Hardware
- UPS Connector
- 
D-Sub-9 Female 
- Communication Interface Pins Assignment
- 
Pin No. Signal Description 2 RXD RS232 receive data (Output data from UPS to PC) 3 TXD RS232 transmit data (Input data from PC to UPS) 4 DTR +12Vdc 5 GND Signal ground 6 BATT LOW This pin triggers an active-low signal in battery low condition 8 BATT MODE This pin triggers an active-low signal in UPS backup mode 1, 7, 9 UNUSED 
- RS232 Technical Specification Summary
- 
Connector 
 9 pin, Type D, Female Format 
 ASCII 8 bit, 1 start bit, 1 stop bit Baud Rate 
 1200 bps Parity 
 None Duplex 
 Full 
Message Format
<Header 1 byte><Message Type 1 byte><Data Length 3 bytes><Data 128bytes max>
Where:
- 
Header
- 
is a ^(carat) character
- 
Message Type
- 
will be one of the following: 0
 Command rejected (from UPS to PC) 1
 Command accepted (from UPS to PC) P
 Poll command (from PC to UPS) S
 Set command (from PC to UPS) D
 Data returned (from UPS to PC) 
- 
Data Length
- 
is the number of bytes of data passed 
- 
Data
- 
is comma delimited. If a variable value is unavailable, a comma with no data is placed in the variable location. For example, if only the 2nd, 4th, and 6th variables have valid data, the UPS response will have the following format: ^D010,1,,22,,82
Poll Commands
| Command | Description | Max Data Length | Variables Returned | 
|---|---|---|---|
| 
 | UPS manufacturer | 32 | Manufacturer | 
| 
 | UPS model | 64 | UPS model | 
| 
 | Status group 1 - Battery | 32 | ,Battery status ,,,, Estimated charge | 
| 
 | Status group 2 - Input | 65 | ,Input num lines, Input frequency 1, Input voltage 1 | 
| 
 | Status group 3 - Output | 66 | Output source, Output frequency, Output num lines, Output voltage 1,,,Output load1 | 
| 
 | UPS version | 32 | UPS firmware and/or software version | 
UPS Status
ST1 command will return up to 32 bytes of data (including commas).
All values are comma delimited.
| Variable Name | Max Length | Units | 
|---|---|---|
| Battery status | 1 | 
 | 
| Estimated Charge | 3 | Percent | 
ST2 command will return up to 65 bytes of data (including commas).
All values are comma delimited.
| Variable Name | Max Length | Units | 
|---|---|---|
| Input num lines | 1 | Integer (1-3) | 
| Input frequency 1 | 3 | 0.1 Hz | 
| Input voltage 1 | 4 | 0.1 volts | 
ST3 command will return up to 66 bytes of data (including commas).
All values are delimited.
| Variable Name | Max Length | Units | 
|---|---|---|
| Output source | 1 | 
 | 
| Output frequency | 3 | 0.1 Hz | 
| Output num lines | 1 | Integer (1-3) | 
| Output voltage 1 | 4 | 0.1 volts | 
| Output load 1 | 3 | Percent | 
Set Commands
| Command | Description | Max Length | Data | Variable Set | 
|---|---|---|---|---|
| 
 | Performs UPS shutdown after the indicated no. of seconds | 7 | 
 | Shutdown After Delay | 
| 
 | Immediately perform UPS shutdown, then restarts after indicated no. of seconds | 7 | Seconds | Reboot with Duration | 
| 
 | Starts UPS after indicated no. of seconds | 7 | 
 | Startup After Delay | 
| 
 | Test UPS | 2 | 
 | Test Type | 
Communication Examples
- 
Host PC requests for UPS manufacturer: ^P003MANUPS responds: ^D014PK ELECTRONICS014
 14 bytes to follow PK ELECTRONICS
 Manufacturer 
- 
Host PC requests for UPS model: ^P003MODUPS responds: ^D006US9003006
 6 bytes to follow US9003
 Model 
- 
Host PC requests for UPS status input parameters: ^P003ST2UPS responds: ^D011,1,500,2350011
 11 bytes to follow 1
 Input num lines (single phase UPS) 500
 Input frequency 1 of 50.0 Hz 2350
 Input voltage 1 of 235.0 Volts 
- 
Host PC attempts to shutdown UPS: ^S006PSD120006
 6 bytes to follow PSD120
 Shutdown UPS in 2 minutes UPS responds: ^11
 Command accepted 
- 
Host PC attempts to reboot UPS: ^S006RWD300006
 6 bytes to follow RWD300
 Shutdown UPS immediately and restarts it after 5 minutes UPS responds: ^11
 Command accepted 

 