Network UPS Tools
Power Devices support
Table of Contents

Click here to see reports of other supported models from APC.

Note

When a user reports that a variable/command is not right then it will be highlighted by a red underline.

Bad values/ranges/etc… will get a red dashed outline or red solid left border.

The accompanying explaining comment - if provided - will be emphasized through a red dotted border on the left.

2.1.0

Report #1 with driver snmp-ups (detailed comments available)

This device is known to work with driver snmp-ups.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Some more detailed comments are available after the "Known supported…" sections.

Known supported variables

This device is known to support the following variables (values are just examples):

ambient.humidity

032.0

ambient.temperature

025.0

battery.charge

100.0

battery.charge.low

120

battery.charge.restart

0

battery.runtime

1080.0

battery.voltage

439.0

driver.name

snmp-ups

driver.parameter.mibs

apcc

driver.parameter.port

ups.hpc2n.umu.se

driver.parameter.snmp_version

v1

driver.version

2.1.0

driver.version.internal

0.41

input.L1-L2.voltage

393.0

input.L1-L2.voltage.maximum

413.0

input.L1-L2.voltage.minimum

000.0

input.L1.current

137.0

input.L1.current.maximum

160.0

input.L1.current.minimum

000.0

input.L2-L3.voltage

397.0

input.L2-L3.voltage.maximum

499.0

input.L2-L3.voltage.minimum

000.0

input.L2.current

154.0

input.L2.current.maximum

178.0

input.L2.current.minimum

000.0

input.L3-L1.voltage

390.0

input.L3-L1.voltage.maximum

409.0

input.L3-L1.voltage.minimum

000.0

input.L3.current

146.0

input.L3.current.maximum

170.0

input.L3.current.minimum

000.0

input.frequency

000.0

input.phases

3

input.sensitivity

high

input.transfer.high

460

input.transfer.low

340

input.voltage

227.0

output.L1-L2.voltage

403.0

output.L1.current

133.0

output.L1.current.maximum

154.0

output.L1.current.minimum

002.0

output.L1.power

30900.0

output.L1.power.maximum

36100.0

output.L1.power.maximum.percent

090.0

output.L1.power.minimum

500.0

output.L1.power.minimum.percent

001.0

output.L1.power.percent

077.0

output.L2-L3.voltage

402.0

output.L2.current

153.0

output.L2.current.maximum

178.0

output.L2.current.minimum

002.0

output.L2.power

35300.0

output.L2.power.maximum

41300.0

output.L2.power.maximum.percent

103.0

output.L2.power.minimum

500.0

output.L2.power.minimum.percent

001.0

output.L2.power.percent

088.0

output.L3-L1.voltage

400.0

output.L3.current

141.0

output.L3.current.maximum

154.0

output.L3.current.minimum

002.0

output.L3.power

32600.0

output.L3.power.maximum

35700.0

output.L3.power.maximum.percent

089.0

output.L3.power.minimum

500.0

output.L3.power.minimum.percent

001.0

output.L3.power.percent

081.0

output.current

099.0

output.frequency

051.0

output.phases

3

output.voltage

231.0

output.voltage.target.battery

400

ups.delay.shutdown

20

ups.delay.start

0

ups.firmware

329.15.I

ups.load

088.0

ups.mfr

APC

ups.mfr.date

00/00/00

ups.model

Silcon DP3120E

ups.serial

JA0323051572

ups.status

OL

ups.temperature

021.0

ups.test.result

InvalidTest