2.4.3

Report #1 with driver snmp-ups (detailed comments available)

This device is known to work with driver snmp-ups.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Some more detailed comments are available after the "Known supported…" sections.

Known supported variables

This device is known to support the following variables (values are just examples):

ambient.1.humidity.alarm.high

60.00

ambient.1.humidity.alarm.low

30.00

ambient.1.temperature.alarm.high

40.00

ambient.1.temperature.alarm.low

10.00

ambient.humidity

0.00

ambient.temperature

17.0

battery.charge

100.00

battery.charge.restart

0

battery.current

0.00

battery.current.total

0.00

battery.date

01/27/13

battery.packs

1.00

battery.runtime

3000.00

battery.runtime.low

120

battery.voltage

218.10

device.mfr

APC

device.model

Smart-UPS RT 6000 XL

device.serial

QS1305270257

device.type

ups

driver.name

snmp-ups

driver.parameter.pollinterval

2

driver.parameter.port

apc1.local.domain

driver.parameter.synchronous

no

driver.version

nut-2_4_3-5_fc14-118-g9c491d9

driver.version.data

apcc MIB 1.2

driver.version.internal

0.97

input.frequency

60.00

input.sensitivity

UNKNOWN

input.transfer.high

229

input.transfer.low

146

input.transfer.reason

selfTest

input.voltage

213.10

input.voltage.maximum

214.50

input.voltage.minimum

211.60

output.current

6.00

output.frequency

60.00

output.voltage

207.00

output.voltage.nominal

208

ups.delay.shutdown

20

ups.delay.start

0

ups.firmware

452.18.W

ups.id

UPS_IDEN

ups.load

20.00

ups.mfr

APC

ups.mfr.date

01/27/13

ups.model

Smart-UPS RT 6000 XL

ups.serial

QS1305270257

ups.status

OL

ups.temperature

20.10

ups.test.date

05/18/2020

ups.test.result

Ok

About this device

Note: No matching MIB found for sysOID .1.3.6.1.4.1.318.1.3.2!