Report #1 with driver usbhid-ups (detailed comments available)

This device is known to work with driver usbhid-ups.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Some more detailed comments are available after the "Known supported…" sections.

Known supported variables

This device is known to support the following variables (values are just examples):

battery.charge

100

battery.charge.low

10

This variable can be set through upsrw to a string value upto the length of 10 characters.

battery.charge.warning

20

battery.mfr.date

CPS

battery.runtime

2640

battery.runtime.low

300

This variable can be set through upsrw to a string value upto the length of 10 characters.

battery.type

PbAcid

battery.voltage

24.0

see CP1500PFCLCD; might be constant

battery.voltage.nominal

24

device.mfr

CP1500EPFCLCD

device.model

CRJB103.551

device.serial

CPS

device.type

ups

driver.name

usbhid-ups

driver.parameter.pollfreq

30

driver.parameter.pollinterval

2

driver.parameter.port

auto

driver.parameter.synchronous

no

driver.version

2.7.3

driver.version.data

CyberPower HID 0.4

driver.version.internal

0.39

input.transfer.high

260

This variable can be set through upsrw to a string value upto the length of 10 characters.

input.transfer.low

170

This variable can be set through upsrw to a string value upto the length of 10 characters.

input.voltage

237.0

input.voltage.nominal

230

output.voltage

269.0

varies, but does not match LCD

ups.beeper.status

disabled

ups.delay.shutdown

20

This variable can be set through upsrw to a string value upto the length of 10 characters.

ups.delay.start

30

This variable can be set through upsrw to a string value upto the length of 10 characters.

ups.load

19

ups.mfr

CP1500EPFCLCD

ups.model

CRJB103.551

does not match barcode or other serial number on device.

ups.productid

0501

ups.realpower.nominal

900

ups.serial

CPS

ups.status

OL

ups.test.result

No test initiated

ups.timer.shutdown

-60

ups.timer.start

-60

ups.vendorid

0764

Known supported commands

This device is known to support the following NUT’s instant commands:

  • beeper.disable

  • beeper.enable

  • beeper.mute

  • beeper.off

  • beeper.on

  • load.off

  • load.off.delay

  • load.on

  • load.on.delay

  • shutdown.return

  • shutdown.stayoff

  • shutdown.stop

  • test.battery.start.deep

  • test.battery.start.quick

  • test.battery.stop

About this device

Shutdown sequence tested with NUT 2.7.3.