When a user reports that a variable/command is not right then it will be highlighted by a red underline. Bad values/ranges/etc… will get a red dashed outline or red solid left border. The accompanying explaining comment - if provided - will be emphasized through a red dotted border on the left. |
2.7.4
Report #1 with driver usbhid-ups (detailed comments available)
This device is known to work with driver usbhid-ups.
You can grab a dummy-ups compliant .dev
file to simulate this device clicking here.
Some more detailed comments are available after the "Known supported…" sections.
Known supported variables
This device is known to support the following variables (values are just examples):
battery.charge
|
|
battery.charge.low
|
|
battery.charge.warning
|
|
battery.mfr.date
|
|
battery.runtime
|
|
battery.runtime.low
|
|
battery.type
|
|
battery.voltage
|
|
battery.voltage.nominal
|
|
device.mfr
|
|
device.model
|
|
device.serial
|
|
device.type
|
|
driver.name
|
|
driver.parameter.pollfreq
|
|
driver.parameter.pollinterval
|
|
driver.parameter.port
|
|
driver.parameter.synchronous
|
|
driver.version
|
|
driver.version.data
|
|
driver.version.internal
|
|
input.voltage
|
|
input.voltage.nominal
|
|
output.voltage
|
|
ups.beeper.status
|
|
ups.delay.shutdown
|
|
ups.delay.start
|
|
ups.load
|
|
ups.mfr
|
|
ups.model
|
|
ups.productid
|
|
ups.realpower.nominal
|
|
ups.serial
|
|
ups.status
|
|
ups.test.result
|
|
ups.timer.shutdown
|
|
ups.timer.start
|
|
ups.vendorid
|
|
About this device
Tested shutdown and the master and all slaves shutdown at LB as expected (35%)
Some commands don’t appear to work when sent through upscmd
and upsrw
.
The battery.charge.low
value doesn’t seem to be user changeable (known issue).
Some of the reported values appear off as well: output.voltage
I would
expect to be 120V and the battery voltages also appear incorrect.
The UPS LCD reports 4 12V cells in series for 48V nominal 54V actual.
Reported at:
Vendor/Manufacturer information:
Further system data or configuration examples:
upsrw ups@localhost
listing# TODO: Convert to RW:... and RO:... markup
:; upsrw ups@localhost
[battery.charge.low]
Remaining battery level when UPS switches to LB (percent)
Type: STRING
Maximum length: 10
Value: 35
[battery.runtime.low]
Remaining battery runtime when UPS switches to LB (seconds)
Type: STRING
Maximum length: 10
Value: 300
[ups.delay.shutdown]
Interval to wait after shutdown with delay command (seconds)
Type: STRING
Maximum length: 10
Value: 20
[ups.delay.start]
Interval to wait before (re)starting the load (seconds)
Type: STRING
Maximum length: 10
Value: 30
upscmd -l ups@localhost
listing# TODO: Convert to CMD:... markup
:; upscmd -l ups@localhost
Instant commands supported on UPS [ups]:
beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
beeper.off - Obsolete (use beeper.disable or beeper.mute)
beeper.on - Obsolete (use beeper.enable)
load.off - Turn off the load immediately
load.off.delay - Turn off the load with a delay (seconds)
load.on - Turn on the load immediately
load.on.delay - Turn on the load with a delay (seconds)
shutdown.return - Turn off the load and return when power is back
shutdown.stayoff - Turn off the load and remain off
shutdown.stop - Stop a shutdown in progress
test.battery.start.deep - Start a deep battery test
test.battery.start.quick - Start a quick battery test
test.battery.stop - Stop the battery test