Network UPS Tools
Power Devices support
Table of Contents

Click here to see reports of other supported models from Cyber Power Systems.

Note

When a user reports that a variable/command is not right then it will be highlighted by a red underline.

Bad values/ranges/etc… will get a red dashed outline or red solid left border.

The accompanying explaining comment - if provided - will be emphasized through a red dotted border on the left.

2.4.3

Report #1 with driver usbhid-ups (detailed comments available)

This device is known to work with driver usbhid-ups.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Some more detailed comments are available after the "Known supported…" sections.

Known supported variables

This device is known to support the following variables (values are just examples):

battery.charge

100

battery.charge.low

10

battery.charge.warning

20

battery.mfr.date

CPS

battery.runtime

3270

battery.runtime.low

300

battery.type

PbAcid

battery.voltage

13.9

battery.voltage.nominal

24

device.mfr

CPS

device.model

Value 2200E

device.type

ups

driver.name

usbhid-ups

driver.parameter.offdelay

60

driver.parameter.ondelay

70

driver.parameter.pollfreq

30

driver.parameter.pollinterval

2

driver.parameter.port

auto

driver.parameter.productid

0501

driver.parameter.vendorid

0764

driver.version

2.4.3

driver.version.data

CyberPower HID 0.3

driver.version.internal

0.34

input.transfer.high

263

input.transfer.low

-96

input.voltage

240.0

input.voltage.nominal

230

output.voltage

240.0

ups.beeper.status

enabled

ups.delay.shutdown

20

ups.delay.start

30

ups.load

14

ups.mfr

CPS

ups.model

Value 2200E

ups.productid

0501

ups.realpower.nominal

296

ups.status

FSD OL

ups.test.result

Done and passed

ups.timer.shutdown

-60

ups.timer.start

0

ups.vendorid

0764