Network UPS Tools
Power Devices support
Table of Contents

Click here to see reports of other supported models from Eaton.

Note

When a user reports that a variable/command is not right then it will be highlighted by a red underline.

Bad values/ranges/etc… will get a red dashed outline or red solid left border.

The accompanying explaining comment - if provided - will be emphasized through a red dotted border on the left.

2.7.2

Report #1 with driver mge-shut (detailed comments available)

This device is known to work with driver mge-shut.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Some more detailed comments are available after the "Known supported…" sections.

Known supported variables

This device is known to support the following variables (values are just examples):

battery.capacity

9.00

battery.charge

95

battery.charge.low

1

battery.charge.restart

0

battery.protection

yes

battery.runtime

7795

battery.runtime.low

180

battery.type

PbAc

device.mfr

EATON

device.model

Eaton 9PX 2000 RT

device.serial

GA19H21231

device.type

ups

driver.name

mge-shut

driver.parameter.pollfreq

30

driver.parameter.pollinterval

2

driver.parameter.port

/dev/ttyU0

driver.version

2.7.2

driver.version.data

MGE HID 1.33

driver.version.internal

0.38

input.frequency.nominal

60

input.voltage.nominal

120

outlet.1.status

on

output.current

1.50

output.frequency

60.0

output.frequency.nominal

60

output.powerfactor

0.83

output.voltage.nominal

120

ups.beeper.status

enabled

ups.date

2018/03/16

ups.delay.shutdown

20

ups.delay.start

30

ups.efficiency

75

ups.firmware


ups.load

9

ups.mfr

EATON

ups.model

Eaton 9PX 2000 RT

ups.power

180

ups.power.nominal

2000

ups.productid

ffff

ups.realpower

150

ups.realpower.nominal

1800

ups.serial

GA19H21231

ups.shutdown

enabled

ups.status

OL CHRG

ups.temperature

17.9

ups.test.interval

2592000

ups.test.result

Done and passed

ups.time

00:32:58

ups.timer.shutdown

0

ups.timer.start

0

ups.type

online

ups.vendorid

0463

About this device

Reported at:

Vendor/Manufacturer information:

Further system data or configuration examples:

Variables per upsrw eaton9px@localhost listing
# TODO: Convert to RW:... and RO:... markup
:; upsrw eaton9px@localhost
[battery.charge.low]
Remaining battery level when UPS switches to LB (percent)
Type: STRING
Maximum length: 5
Value: 1

[battery.charge.restart]
Minimum battery level for restart after power off (percent)
Type: STRING
Maximum length: 3
Value: 0

[battery.protection]
Prevent deep discharge of battery
Type: STRING
Maximum length: 5
Value: yes

[battery.runtime.low]
Remaining battery runtime when UPS switches to LB (seconds)
Type: STRING
Maximum length: 10
Value: 180

[output.voltage.nominal]
Nominal output voltage (V)
Type: ENUM
Option: "100"
Option: "110"
Option: "120" SELECTED
Option: "127"

[ups.date]
Internal UPS clock date
Type: STRING
Maximum length: 10
Value: 2018/03/16

[ups.delay.shutdown]
Interval to wait after shutdown with delay command (seconds)
Type: STRING
Maximum length: 10
Value: 20

[ups.delay.start]
Interval to wait before (re)starting the load (seconds)
Type: STRING
Maximum length: 10
Value: 30

[ups.shutdown]
Description unavailable
Type: ENUM
Option: "disabled"
Option: "enabled" SELECTED

[ups.test.interval]
Interval between self tests (seconds)
Type: STRING
Maximum length: 8
Value: 2592000

[ups.time]
Internal UPS clock time
Type: STRING
Maximum length: 10
Value: 01:43:33
Commands per upscmd -l eaton9px@localhost listing
# TODO: Convert to CMD:... markup
:; upscmd -l eaton9px@localhost
Instant commands supported on UPS [eaton9px]:
beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
beeper.off - Obsolete (use beeper.disable or beeper.mute)
beeper.on - Obsolete (use beeper.enable)
load.off - Turn off the load immediately
load.off.delay - Turn off the load with a delay (seconds)
load.on - Turn on the load immediately
load.on.delay - Turn on the load with a delay (seconds)
shutdown.return - Turn off the load and return when power is back
shutdown.stayoff - Turn off the load and remain off
shutdown.stop - Stop a shutdown in progress
test.battery.start.deep - Start a deep battery test
test.battery.start.quick - Start a quick battery test
test.battery.stop - Stop the battery test