Report #1 with driver nutdrv_qx (detailed comments available)
This device is known to work with driver nutdrv_qx.
You can grab a dummy-ups compliant .dev
file to simulate this device clicking here.
Some more detailed comments are available after the "Known supported…" sections.
Known supported variables
This device is known to support the following variables (values are just examples):
battery.charge
|
|
battery.runtime
|
|
battery.voltage
|
|
battery.voltage.high
|
|
battery.voltage.low
|
|
battery.voltage.nominal
|
|
device.model
|
|
device.type
|
|
driver.name
|
|
driver.parameter.bus
|
|
driver.parameter.chargetime
|
|
driver.parameter.idleload
|
|
driver.parameter.offdelay
|
|
driver.parameter.ondelay
|
|
driver.parameter.pollfreq
|
|
driver.parameter.pollinterval
|
|
driver.parameter.port
|
|
driver.parameter.product
|
|
driver.parameter.productid
|
|
driver.parameter.runtimecal
|
|
driver.parameter.synchronous
|
|
driver.parameter.vendor
|
|
driver.parameter.vendorid
|
|
driver.version
|
|
driver.version.data
|
|
driver.version.internal
|
|
input.current.nominal
|
|
input.frequency
|
|
input.frequency.nominal
|
|
input.voltage
|
|
input.voltage.fault
|
|
input.voltage.nominal
|
|
output.voltage
|
|
ups.beeper.status
|
|
ups.delay.shutdown
|
UPS ignores this; constant 30 second delay |
ups.delay.start
|
UPS ignores this; constant 10 second delay |
ups.firmware
|
|
ups.load
|
|
ups.productid
|
|
ups.status
|
|
ups.temperature
|
temperature is constant |
ups.type
|
|
ups.vendorid
|
|
Known supported commands
This device is known to support the following NUT’s instant commands:
-
beeper.toggle
-
if the beeper emits a beep at the time when command is issued the beep never ends…
-
the beeper can not be switched off if UPS is on line,
-
nutdrv_qx output:
396.231354 instcmd(beeper.toggle, [NULL]) 396.231400 send: Q 396.231414 command index: 0x07 396.250914 read: UPS No Ack 396.250947 instcmd: FAILED
-
-
load.off
-
load are switched off after ~30s,
-
shutdown.stop (
C
command) will not break the shutdown, -
nutdrv_qx output: http://bpa.ksu.pl/pub/nutdrv_qx_load.off.txt (4kB)
-
-
load.on
-
load are switched on after ~10s,
-
nutdrv_qx output: http://bpa.ksu.pl/pub/nutdrv_qx_load.on.txt (2kB)
-
-
shutdown.return
-
load is switched on immediately, ups.delay.start (
R<n>
part of the command, as inS01R0001
) does not matter, -
shutdown.stop (
C
command) can break the shutdown, -
nutdrv_qx output: http://bpa.ksu.pl/pub/nutdrv_qx_shutdown.return.txt (7kB)
-
-
shutdown.stayoff
-
shutdown.stop (
C
command) will not break the shutdown, -
nutdrv_qx output: http://bpa.ksu.pl/pub/nutdrv_qx_shutdown.stayoff.txt (7kB)
-
-
shutdown.stop
Stop only shutdown.return
About this device
Vendor site: http://fideltronikinigo.com/viper/viper-1200/
The blazer_usb driver did not work with this device.
test.battery.*
commands were presented by driver, but do not work.
Source and additional logs: http://lists.alioth.debian.org/pipermail/nut-upsdev/2015-July/007025.html
Reported at: