Network UPS Tools
Power Devices support
Table of Contents

Click here to see reports of other supported models from HP.

Note

When a user reports that a variable/command is not right then it will be highlighted by a red underline.

Bad values/ranges/etc… will get a red dashed outline or red solid left border.

The accompanying explaining comment - if provided - will be emphasized through a red dotted border on the left.

2.4.3

Report #1 with driver bcmxcp (detailed comments available)

This device is known to work with driver bcmxcp.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Some more detailed comments are available after the "Known supported…" sections.

Known supported variables

This device is known to support the following variables (values are just examples):

ambient.temperature

27.4

ambient.temperature.high

45

battery.charge

99.0

battery.runtime

536

battery.voltage

236.3

device.mfr

Eaton

device.model

HP R5000 5000i

device.serial

3C81520083

device.type

ups

driver.name

bcmxcp

driver.parameter.baud_rate

9600

driver.parameter.pollinterval

2

driver.parameter.port

/dev/ttyS0

driver.version

2.4.3

driver.version.internal

0.23

input.current

18.1

input.frequency

50.0

input.frequency.high

54

input.frequency.low

46

input.frequency.nominal

50

input.transfer.boost.high

202

input.transfer.high

288

input.transfer.low

176

input.transfer.trim.low

257

input.voltage

224.1

input.voltage.nominal

230

outlet.1.delay.shutdown

-1

outlet.1.delay.start

0

outlet.1.id

1

outlet.1.status

On

outlet.2.delay.shutdown

258

outlet.2.delay.start

-1

outlet.2.id

0

outlet.2.status

Off

output.current

16.4

output.current.nominal

21.7

output.frequency

50.0

output.phases

1

output.voltage

222.2

output.voltage.nominal

230

ups.beeper.status

muted

ups.firmware

Cont:01.02 Inve:01.02

ups.load

73.1

ups.mfr

Eaton

ups.model

HP R5000 5000i

ups.power

3655.0

ups.power.nominal

5000

ups.serial

3C81520083

ups.status

OL

Known supported commands

This device is known to support the following NUT’s instant commands:

  • outlet.1.shutdown.return

  • outlet.2.shutdown.return

  • shutdown.return

  • shutdown.stayoff

  • test.battery.start