Network UPS Tools
Power Devices support
Table of Contents

Click here to see reports of other supported models from Ippon.

Note

When a user reports that a variable/command is not right then it will be highlighted by a red underline.

Bad values/ranges/etc… will get a red dashed outline or red solid left border.

The accompanying explaining comment - if provided - will be emphasized through a red dotted border on the left.

2.7.4

Report #1 with driver usbhid-ups (detailed comments available)

This device is known to work with driver usbhid-ups.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Some more detailed comments are available after the "Known supported…" sections.

Known supported variables

This device is known to support the following variables (values are just examples):

battery.charge

100

battery.runtime

4520

battery.type

PbAc

battery.voltage

28

device.mfr

PPC

device.model

Offline UPS

device.serial

000000000

device.type

ups

driver.name

usbhid-ups

driver.parameter.pollfreq

30

driver.parameter.pollinterval

10

driver.parameter.port

auto

driver.parameter.synchronous

yes

driver.version

2.7.4

driver.version.data

Phoenixtec/Liebert HID 0.3

driver.version.internal

0.41

ups.load

5

ups.mfr

PPC

ups.model

Offline UPS

ups.productid

ffff

ups.serial

000000000

ups.status

OL CHRG

ups.vendorid

06da

About this device

I’ve got a new Ippon UPS "Smart Power Pro II 1200" and neither Input nor Output voltage values are reported/shown by nut.

The same problem probably applies to the whole family of new(?) Ippon devices with a display - SMART POWER PRO II 1200/1600/2200 and SMART POWER PRO II EURO 1200/1600/2200.

For an issue with regular disconnections, see also: https://github.com/networkupstools/nut/issues/786

Regarding driver data dump below:

  • It seems that driver just ignores some paths:

    • Path: UPS.PowerConverter.Input.[1].Voltage, Type: Feature, ReportID: 0x31, Offset: 0, Size: 16, Value: 225

    • Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x42, Offset: 16, Size: 16, Value: 225

  • Other parameters like frequency data is available on UPS as well, but not seen by the driver.

Another problem that it is not possible to send commands to the UPS, for example, to disable beep - the list of commands is empty.

"Same thing" (problems?) also reported for Ippon Smart Power Pro II 1600.

More information seems to be available with custom builds using an MGE and not Liebert subdriver (shared USB identification).

Reported at:

Further system data or configuration examples:

Driver configuration
[ups]
    driver = usbhid-ups
    port = auto
    desc = "Ippon Smart Power Pro II 1200"
    synchronous = yes
    pollinterval = 10
Driver data dump
:; /lib/nut/usbhid-ups -D -a ups -u root
Network UPS Tools - Generic HID driver 0.41 (2.7.4)
USB communication driver 0.33
0.000000 debug level is '1'
0.001405 upsdrv_initups...
0.142334 Using subdriver: Phoenixtec/Liebert HID 0.3
0.142385 45 HID objects found
0.144121 Path: UPS.BatterySystem.Battery.Test, Type: Feature, ReportID: 0x24, Offset: 0, Size: 8, Value: 6
0.146117 Path: UPS.Flow.[4].ConfigApparentPower, Type: Feature, ReportID: 0x74, Offset: 0, Size: 16, Value: 5
0.148099 Path: UPS.Flow.[4].ConfigFrequency, Type: Feature, ReportID: 0x36, Offset: 0, Size: 8, Value: 50
0.150099 Path: UPS.Flow.[4].ConfigVoltage, Type: Feature, ReportID: 0x72, Offset: 0, Size: 8, Value: 220
0.152099 Path: UPS.PowerConverter.ffff0041, Type: Feature, ReportID: 0x4a, Offset: 0, Size: 8, Value: 1
0.154127 Path: UPS.PowerConverter.Input.[1].Voltage, Type: Feature, ReportID: 0x31, Offset: 0, Size: 16, Value: 225
0.156105 Path: UPS.PowerConverter.Input.[1].PresentStatus.Boost, Type: Feature, ReportID: 0x2d, Offset: 0, Size: 8, Value: 0
0.156136 Path: UPS.PowerConverter.Input.[1].PresentStatus.Boost, Type: Input, ReportID: 0x2d, Offset: 0, Size: 8, Value: 0
0.156178 Path: UPS.PowerConverter.Input.[1].PresentStatus.Buck, Type: Feature, ReportID: 0x2d, Offset: 8, Size: 8, Value: 0
0.156211 Path: UPS.PowerConverter.Input.[1].PresentStatus.Buck, Type: Input, ReportID: 0x2d, Offset: 8, Size: 8, Value: 0
0.158129 Path: UPS.PowerConverter.Output.Frequency, Type: Feature, ReportID: 0x42, Offset: 0, Size: 16, Value: 50
0.158160 Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x42, Offset: 16, Size: 16, Value: 225
0.160107 Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 2
0.162117 Path: UPS.PowerSummary.DelayBeforeShutdown, Type: Feature, ReportID: 0x09, Offset: 0, Size: 32, Value: -1
0.164108 Path: UPS.PowerSummary.DelayBeforeStartup, Type: Feature, ReportID: 0x0a, Offset: 0, Size: 32, Value: -1
0.166106 Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 5
0.166136 Path: UPS.PowerSummary.iManufacturer, Type: Feature, ReportID: 0x10, Offset: 8, Size: 8, Value: 1
0.166174 Path: UPS.PowerSummary.ffff00f0, Type: Feature, ReportID: 0x10, Offset: 16, Size: 8, Value: 3
0.166246 Path: UPS.PowerSummary.iProduct, Type: Feature, ReportID: 0x10, Offset: 24, Size: 8, Value: 2
0.166301 Path: UPS.PowerSummary.iSerialNumber, Type: Feature, ReportID: 0x10, Offset: 32, Size: 8, Value: 4
0.168104 Path: UPS.PowerSummary.ffff00e2, Type: Feature, ReportID: 0xe2, Offset: 0, Size: 8, Value: 4
0.170120 Path: UPS.PowerSummary.PercentLoad, Type: Feature, ReportID: 0x07, Offset: 0, Size: 8, Value: 5
0.172101 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
0.172131 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
0.172167 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
0.172208 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
0.172246 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
0.172298 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
0.172355 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
0.172410 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
0.172461 Path: UPS.PowerSummary.PresentStatus.Good, Type: Feature, ReportID: 0x01, Offset: 32, Size: 8, Value: 1
0.172504 Path: UPS.PowerSummary.PresentStatus.Good, Type: Input, ReportID: 0x01, Offset: 32, Size: 8, Value: 1
0.172538 Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x01, Offset: 40, Size: 8, Value: 0
0.172571 Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Input, ReportID: 0x01, Offset: 40, Size: 8, Value: 0
0.172603 Path: UPS.PowerSummary.PresentStatus.Overload, Type: Feature, ReportID: 0x01, Offset: 48, Size: 8, Value: 0
0.172634 Path: UPS.PowerSummary.PresentStatus.Overload, Type: Input, ReportID: 0x01, Offset: 48, Size: 8, Value: 0
0.174129 Path: UPS.PowerSummary.DesignCapacity, Type: Feature, ReportID: 0x0b, Offset: 0, Size: 8, Value: 100
0.174158 Path: UPS.PowerSummary.CapacityGranularity1, Type: Feature, ReportID: 0x0b, Offset: 8, Size: 8, Value: 1
0.174210 Path: UPS.PowerSummary.FullChargeCapacity, Type: Feature, ReportID: 0x0b, Offset: 16, Size: 8, Value: 100
0.174249 Path: UPS.PowerSummary.CapacityMode, Type: Feature, ReportID: 0x0b, Offset: 24, Size: 8, Value: 2
0.176108 Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
0.176137 Path: UPS.PowerSummary.RemainingCapacity, Type: Input, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
0.176177 Path: UPS.PowerSummary.RunTimeToEmpty, Type: Feature, ReportID: 0x06, Offset: 8, Size: 16, Value: 4520
0.176209 Path: UPS.PowerSummary.RunTimeToEmpty, Type: Input, ReportID: 0x06, Offset: 8, Size: 16, Value: 4520
0.176251 Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x07, Offset: 8, Size: 16, Value: 27.5
0.176291 Detected a UPS: PPC/Offline UPS
0.180164 upsdrv_initinfo...
0.180195 upsdrv_updateinfo...
0.431114 Got 0 HID objects...
0.431155 Quick update...
0.431341 upsdrv_updateinfo...
0.683333 Got 0 HID objects...
0.683432 Quick update...