Network UPS Tools
Power Devices support
Table of Contents

Click here to see reports of other supported models from APC.

Note

When a user reports that a variable/command is not right then it will be highlighted by a red underline.

Bad values/ranges/etc… will get a red dashed outline or red solid left border.

The accompanying explaining comment - if provided - will be emphasized through a red dotted border on the left.

2.1.0

Report #1

This device is known to work with driver snmp-ups.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Known supported variables

This device is known to support the following variables (values are just examples):

ambient.humidity

032.0

ambient.temperature

025.0

battery.charge

100.0

battery.charge.low

120

battery.charge.restart

0

battery.runtime

1080.0

battery.voltage

439.0

driver.name

snmp-ups

driver.parameter.mibs

apcc

driver.parameter.port

ups.hpc2n.umu.se

driver.parameter.snmp_version

v1

driver.version

2.1.0

driver.version.internal

0.41

input.L1-L2.voltage

393.0

input.L1-L2.voltage.maximum

413.0

input.L1-L2.voltage.minimum

000.0

input.L1.current

137.0

input.L1.current.maximum

160.0

input.L1.current.minimum

000.0

input.L2-L3.voltage

397.0

input.L2-L3.voltage.maximum

499.0

input.L2-L3.voltage.minimum

000.0

input.L2.current

154.0

input.L2.current.maximum

178.0

input.L2.current.minimum

000.0

input.L3-L1.voltage

390.0

input.L3-L1.voltage.maximum

409.0

input.L3-L1.voltage.minimum

000.0

input.L3.current

146.0

input.L3.current.maximum

170.0

input.L3.current.minimum

000.0

input.frequency

000.0

input.phases

3

input.sensitivity

high

input.transfer.high

460

input.transfer.low

340

input.voltage

227.0

output.L1-L2.voltage

403.0

output.L1.current

133.0

output.L1.current.maximum

154.0

output.L1.current.minimum

002.0

output.L1.power

30900.0

output.L1.power.maximum

36100.0

output.L1.power.maximum.percent

090.0

output.L1.power.minimum

500.0

output.L1.power.minimum.percent

001.0

output.L1.power.percent

077.0

output.L2-L3.voltage

402.0

output.L2.current

153.0

output.L2.current.maximum

178.0

output.L2.current.minimum

002.0

output.L2.power

35300.0

output.L2.power.maximum

41300.0

output.L2.power.maximum.percent

103.0

output.L2.power.minimum

500.0

output.L2.power.minimum.percent

001.0

output.L2.power.percent

088.0

output.L3-L1.voltage

400.0

output.L3.current

141.0

output.L3.current.maximum

154.0

output.L3.current.minimum

002.0

output.L3.power

32600.0

output.L3.power.maximum

35700.0

output.L3.power.maximum.percent

089.0

output.L3.power.minimum

500.0

output.L3.power.minimum.percent

001.0

output.L3.power.percent

081.0

output.current

099.0

output.frequency

051.0

output.phases

3

output.voltage

231.0

output.voltage.target.battery

400

ups.delay.shutdown

20

ups.delay.start

0

ups.firmware

329.15.I

ups.load

088.0

ups.mfr

APC

ups.mfr.date

00/00/00

ups.model

Silcon DP3120E

ups.serial

JA0323051572

ups.status

OL

ups.temperature

021.0

ups.test.result

InvalidTest