Network UPS Tools
Power Devices support
Table of Contents

Click here to see reports of other supported models from Cyber Power Systems.

Note

When a user reports that a variable/command is not right then it will be highlighted by a red underline.

Bad values/ranges/etc… will get a red dashed outline or red solid left border.

The accompanying explaining comment - if provided - will be emphasized through a red dotted border on the left.

2.1.0

Report #1

This device is known to work with driver powerpanel.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Known supported variables

This device is known to support the following variables (values are just examples):

battery.charge

100.0

battery.charge.low

20

driver.name

powerpanel

driver.parameter.pollinterval

2

driver.parameter.port

/dev/ttyUSB0

driver.version

2.1.0

driver.version.internal

0.11

input.frequency

50

input.frequency.high

063

input.frequency.low

047

input.transfer.high

270

input.transfer.low

180

input.voltage

233

input.voltage.nominal

230

output.voltage

233

ups.firmware

2.102

ups.load

28

ups.mfr

CYBER POWER

ups.model

1000VA

ups.power.nominal

1000

ups.realpower.nominal

0700

ups.serial

000000000000

ups.status

OL

ups.temperature

39

2.0.5

Report #1

This device is known to work with driver cpsups, now replaced by the powerpanel one.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Known supported variables

This device is known to support the following variables (values are just examples):

battery.charge

100.0

battery.runtime

36:00

driver.name

cpsups

driver.parameter.port

/dev/ttyUSB0

driver.version

2.0.5-pre1

driver.version.internal

.05

input.frequency

50

input.voltage

231

output.voltage

231

ups.load

28

ups.mfr

MicroDowell

ups.model

B.Box BP 1000 2.102

ups.power.nominal

1000

ups.runtime

50

ups.status

OL

ups.temperature

39