2.7.4

Report #1

This device is known to work with driver usbhid-ups.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Known supported variables

This device is known to support the following variables (values are just examples):

battery.capacity

9.00

battery.charge

100

battery.charge.low

20

This variable can be set through upsrw to a string value upto the length of 5 characters.

battery.charge.restart

0

This variable can be set through upsrw to a string value upto the length of 3 characters.

battery.charger.status

floating

battery.energysave

no

This variable can be set through upsrw to a string value upto the length of 5 characters.

battery.protection

yes

This variable can be set through upsrw to a string value upto the length of 5 characters.

battery.runtime

1032

battery.type

PbAc

device.mfr

EATON

device.model

Eaton 5PX 2000

device.serial

G098D27047

device.type

ups

driver.name

usbhid-ups

driver.parameter.pollfreq

30

driver.parameter.pollinterval

2

driver.parameter.port

auto

driver.parameter.synchronous

no

driver.parameter.vendorid

0463

driver.version

2.7.4

driver.version.data

MGE HID 1.39

driver.version.internal

0.41

input.current

0.00

input.frequency

49.9

input.frequency.extended

no

This variable can be set through upsrw to a string value upto the length of 5 characters.

input.frequency.nominal

50

input.sensitivity

normal

This variable can be set through upsrw to a string value upto the length of 10 characters.

input.transfer.boost.low

184

This variable can be set through upsrw to a string value upto the length of 5 characters.

input.transfer.high

294

This variable can be set through upsrw to a string value upto the length of 5 characters.

input.transfer.low

160

This variable can be set through upsrw to a string value upto the length of 5 characters.

input.transfer.trim.high

265

This variable can be set through upsrw to a string value upto the length of 5 characters.

input.voltage

235.0

input.voltage.extended

no

This variable can be set through upsrw to a string value upto the length of 5 characters.

input.voltage.nominal

230

outlet.1.autoswitch.charge.low

0

This variable can be set through upsrw to a string value upto the length of 3 characters.

outlet.1.current

1.20

outlet.1.delay.shutdown

65535

This variable can be set through upsrw to a string value upto the length of 5 characters.

outlet.1.delay.start

3

This variable can be set through upsrw to a string value upto the length of 5 characters.

outlet.1.desc

PowerShare Outlet 1

This variable can be set through upsrw to a string value upto the length of 20 characters.

outlet.1.id

1

outlet.1.power

282

outlet.1.powerfactor

57.00

outlet.1.realpower

162

outlet.1.status

on

outlet.1.switchable

yes

outlet.2.autoswitch.charge.low

0

This variable can be set through upsrw to a string value upto the length of 3 characters.

outlet.2.current

0.40

outlet.2.delay.shutdown

65535

This variable can be set through upsrw to a string value upto the length of 5 characters.

outlet.2.delay.start

6

This variable can be set through upsrw to a string value upto the length of 5 characters.

outlet.2.desc

PowerShare Outlet 2

This variable can be set through upsrw to a string value upto the length of 20 characters.

outlet.2.id

2

outlet.2.power

94

outlet.2.powerfactor

72.00

outlet.2.realpower

68

outlet.2.status

on

outlet.2.switchable

yes

outlet.current

1.00

outlet.desc

Main Outlet

This variable can be set through upsrw to a string value upto the length of 20 characters.

outlet.id

0

outlet.power

276

outlet.powerfactor

99.00

outlet.realpower

274

outlet.switchable

no

output.current

2.60

output.frequency

49.9

output.frequency.nominal

50

output.powerfactor

0.82

output.voltage

235.0

output.voltage.nominal

230

This variable can be set through upsrw to one of the following values:

  • 200

  • 208

  • 220

  • 230

  • 240

ups.alarm

Replace battery!

ups.beeper.status

enabled

ups.delay.shutdown

20

This variable can be set through upsrw to a string value upto the length of 10 characters.

ups.delay.start

30

This variable can be set through upsrw to a string value upto the length of 10 characters.

ups.efficiency

95

ups.firmware

06

ups.load

30

ups.load.high

105

This variable can be set through upsrw to a string value upto the length of 5 characters.

ups.mfr

EATON

ups.model

Eaton 5PX 2000

ups.power

611

ups.power.nominal

2000

ups.productid

ffff

ups.realpower

504

ups.realpower.nominal

1800

ups.serial

G098D27047

ups.shutdown

enabled

This variable can be set through upsrw to one of the following values:

  • disabled

  • enabled

ups.start.auto

yes

This variable can be set through upsrw to a string value upto the length of 5 characters.

ups.start.battery

yes

This variable can be set through upsrw to a string value upto the length of 5 characters.

ups.start.reboot

yes

This variable can be set through upsrw to a string value upto the length of 5 characters.

ups.status

ALARM OL CHRG RB

ups.test.interval

604800

This variable can be set through upsrw to a string value upto the length of 8 characters.

ups.test.result

Done and passed

ups.timer.shutdown

0

ups.timer.start

0

ups.type

offline / line interactive

ups.vendorid

0463

Known supported commands

This device is known to support the following NUT’s instant commands:

  • beeper.disable

  • beeper.enable

  • beeper.mute

  • beeper.off

  • beeper.on

  • load.off

  • load.off.delay

  • load.on

  • load.on.delay

  • outlet.1.load.off

  • outlet.1.load.on

  • outlet.2.load.off

  • outlet.2.load.on

  • shutdown.return

  • shutdown.stayoff

  • shutdown.stop

  • test.battery.start.deep

  • test.battery.start.quick

  • test.battery.stop