Network UPS Tools
Power Devices support
Table of Contents

Click here to see reports of other supported models from Fideltronik INIGO.

Note

When a user reports that a variable/command is not right then it will be highlighted by a red underline.

Bad values/ranges/etc… will get a red dashed outline or red solid left border.

The accompanying explaining comment - if provided - will be emphasized through a red dotted border on the left.

2.7.3.1

Report #1

This device is known to work with driver nutdrv_qx.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Known supported variables

This device is known to support the following variables (values are just examples):

battery.charge

100

battery.runtime

600

battery.voltage

27.70

battery.voltage.high

26.00

battery.voltage.low

20.80

battery.voltage.nominal

24.0

device.model

1200VA

device.type

ups

driver.name

nutdrv_qx

driver.parameter.bus

004

driver.parameter.chargetime

28800

driver.parameter.idleload

10

driver.parameter.offdelay

60

driver.parameter.ondelay

60

driver.parameter.pollfreq

30

driver.parameter.pollinterval

2

driver.parameter.port

auto

driver.parameter.product

MEC0003

driver.parameter.productid

0000

driver.parameter.runtimecal

60,100,900,21

driver.parameter.synchronous

no

driver.parameter.vendor

MEC

driver.parameter.vendorid

0001

driver.version

2.7.3.1

driver.version.data

Megatec 0.06

driver.version.internal

0.21

input.current.nominal

5.2

input.frequency

50.0

input.frequency.nominal

50

input.voltage

225.9

input.voltage.fault

225.9

input.voltage.nominal

230

output.voltage

225.9

ups.beeper.status

enabled

ups.delay.shutdown

60

UPS ignores this; constant 30 second delay

ups.delay.start

60

UPS ignores this; constant 10 second delay

ups.firmware

VER 1.00

ups.load

0

ups.productid

0000

ups.status

OL

ups.temperature

25.0

temperature is constant

ups.type

offline / line interactive

ups.vendorid

0001

Known supported commands

This device is known to support the following NUT’s instant commands:

  • beeper.toggle

    • if the beeper emits a beep at the time when command is issued the beep never ends…

    • the beeper can not be switched off if UPS is on line,

    • nutdrv_qx output:

          396.231354  instcmd(beeper.toggle, [NULL])
          396.231400  send: Q
          396.231414  command index: 0x07
          396.250914  read: UPS No Ack
          396.250947  instcmd: FAILED
  • load.off

  • load.on

  • shutdown.return

  • shutdown.stayoff

  • shutdown.stop

    Stop only shutdown.return

About this device

The blazer_usb driver did not work with this device.

test.battery.* commands were presented by driver, but do not work.