Network UPS Tools
Power Devices support
Table of Contents

Click here to see reports of other supported models from Tripp Lite.

Note

When a user reports that a variable/command is not right then it will be highlighted by a red underline.

Bad values/ranges/etc… will get a red dashed outline or red solid left border.

The accompanying explaining comment - if provided - will be emphasized through a red dotted border on the left.

2.6.3

Report #1

This device is known to work with driver usbhid-ups.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Known supported variables

This device is known to support the following variables (values are just examples):

battery.charge

100

battery.charge.low

20

This variable can be set through upsrw to a string value.

battery.charge.warning

20

battery.runtime

62985

battery.temperature

26.9

battery.type

PbAc

battery.voltage

54.0

battery.voltage.nominal

48.0

device.mfr

TRIPPLITE      

device.model

TRIPPLITE UPS  

device.serial

2148ALCPS795100005 

device.type

ups

driver.name

usbhid-ups

driver.parameter.pollfreq

30

driver.parameter.pollinterval

2

driver.parameter.port

auto

driver.version

2.6.3

driver.version.data

TrippLite HID 0.6

driver.version.internal

0.35

input.frequency

59.9

input.transfer.high

150.0

This variable can be set through upsrw to a string value.

input.transfer.high.max

150

input.transfer.high.min

145

input.transfer.low

55.0

This variable can be set through upsrw to a string value.

input.transfer.low.max

60

input.transfer.low.min

55

input.voltage

121.0

input.voltage.nominal

100

output.current

0.00

output.frequency

59.9

output.frequency.nominal

60

output.voltage

100.0

output.voltage.nominal

100

ups.beeper.status

disabled

ups.delay.shutdown

20

This variable can be set through upsrw to a string value.

ups.delay.start

30

This variable can be set through upsrw to a string value.

ups.load

0

ups.mfr

TRIPPLITE      

ups.model

TRIPPLITE UPS  

ups.power

0.0

ups.power.nominal

1500

ups.productid

4004

ups.serial

2148ALCPS795100005 

ups.status

OL

ups.test.result

Done and passed

ups.timer.reboot

0

ups.timer.shutdown

-1

ups.timer.start

0

ups.vendorid

09ae

ups.watchdog.status

0

Known supported commands

This device is known to support the following NUT’s instant commands:

  • beeper.disable

  • beeper.enable

  • beeper.mute

  • beeper.off

  • beeper.on

  • load.off

  • load.off.delay

  • load.on

  • load.on.delay

  • reset.watchdog

  • shutdown.reboot

  • shutdown.return

  • shutdown.stayoff

  • shutdown.stop

  • test.battery.start.deep

  • test.battery.start.quick

  • test.battery.stop