G.7. Text cable references

The following original text references retain their pin diagrams, notes and contributor attribution.

APC Back-UPS RS 500 serial cable

Desc: APC UPS cable - for Back-UPS RS 500
File: apc-rs500-serial.txt
Date: 14 July 2004
Auth: Russell Kroll <rkroll@exploits.org>, Martin Edlman <edlman@fortech.cz>

This document was constructed from a mail from Martin.  He figured out
the pinouts to make the Back-UPS RS 500 work with a normal serial port.
Here are the details:

---

UPS side                        PC side
RJ45 (8 pins)                   DB9F

1 orange/white                  2,8,9
2 orange                        1
3 green/white                   chassis/ground
4 blue                          -
5 blue/white                    -
6 green                         5
7 brown/white                   4,6
8 brown                         -

      +---+
+-----+   +-----+
|               |
+---------------+
 8 7 6 5 4 3 2 1

view from back (cable entry)
---

Note this results in OL=-CTS, LB=DCD, SD=ST, CP=RTS, so it should work
with the existing genericups type 20.

APC cable reference

Desc: APC UPS cables
File: apc.txt
Date: 12 February 2010
Auth: Arjen de Korte <adkorte-guest@alioth.debian.org

http://lists.alioth.debian.org/pipermail/nut-upsuser/2005-August/000118.html

Note that APC UPS serial cable part numbers follow a numbering scheme
where the "940-" prefix identifies them as cables.

       940-1000        straight through cable
       940-0103        null modem cable
       940-0020        Basic Signaling Cable (OB and kill power)
       940-0023        Simple Signaling Cable (OB only)
       940-LL24        Smart Signaling Cable
       940-0095        PnP Cable (see Apcupsd manual for diagram)
       940-0119        Simple Signaling Cable (OB and kill power)
       940-0127        RJ45-10P10C to USB Cable
       940-0128        Simple Signaling Cable for Back-UPS CS

"LL" represents the length:

       00      six feet
       NN      NN feet

The suffix letter represents a minor revision in physical design, or a
change of OEM, _not_ a change of wiring or pin-out, and all cables
differing only in this suffix letter are electrically interchangeable.
Note though the following quote from the APC Discussion Forums:  "At one
point there were a small number of revision D cables [940-0024D] that
had some shielding issues from the manufacturer that could maybe cause
[...] [spontaneous] self-tests)."
+-----------------------------------------------------------------+
|                                                                 |
|  Black APC 940-0024C Smart Signalling UPS Cable Wiring Diagram  |
|  This information is verified and tested to be 100% correct.    |
|                                                                 |
+-----------------------------------------------------------------+
|                                                                 |
|       DB9M(UPS)            2m Cable          DB9F(Computer)     |
|       ---------            --------          --------------     |
|                                                                 |
|         (SHELL)<---------+----//----+----------------<(SHELL)   |
|                          |          |                           |
|                          -          -                           |
|                         | |        | |                          |
|       CHASSIS 9<--------------//---------------------<5 SG      |
|                         | |        | |                          |
|           TXD 2<--------------//---------------------<2 RXD     |
|                         | |        | |                          |
|           RXD 1<--------------//---------------------<3 TXD     |
|                         | |        | |                          |
|                          -          -             +--<1 DCD     |
|                                                   |             |
|                                                   +--<4 DTR     |
|    NOTES:                                                       |
|    Cable type is shielded 28AWG.                  +--<7 RTS     |
|    The DB shells are connected                    |             |
|    to each other via the shield.                  +--<8 CTS     |
|                                                                 |
+-----------------------------------------------------------------+
|                                                                 |
|    Operation:     The UPS communicates with the Computer via    |
|    ordinary RS-232 serial protocol at 2400-8N1 with software    |
|    flow control. Jumpered pins in the DB9F connector are for    |
|    automatic or PNP cable identification by UPS software.       |
|                                                                 |
+-----------------------------------------------------------------+
|                                                                 |
|                           Male (pins)        Female (holes)     |
|   DB9 RS-232  PC                                                |
|   type connector          1         5         5         1       |
|  ----------------       _______________     _______________     |
|  Pinout numbering       \  . . . . .  /     \  o o o o o  /     |
|  looking into the        \  . . . .  /       \  o o o o  /      |
|  end of the cable         -----------         -----------       |
|                             6     9             9     6         |
|                                                                 |
|  NOTE: Solder a wire to the metal shell for use as a FRAME-GND  |
|                                                                 |
+-----------------------------------------------------------------+
+-----------------------------------------------------------------+
|                                                                 |
|  Gray APC 940-0020B Simple Signalling UPS Cable Wiring Diagram  |
|  This information is verified and tested to be 100% correct.    |
|                                                                 |
+-----------------------------------------------------------------+
|                                                                 |
|      DB9M(UPS)          2m Cable             DB9F(Computer)     |
|      ---------          --------             --------------     |
|                                                                 |
|        (SHELL)<-------+----//----+-------------------<(SHELL)   |
|                       |          |                              |
|      CHASSIS 9<--+    -          -                              |
|                  |   | |        | |                             |
|       COMMON 4<--+---------//------------------------<5 SG      |
|                      | |        | |                             |
|   POWER-FAIL 2<------------//------------------------<8 CTS     |
|                      | |        | |                             |
|     SHUTDOWN 1<------------//------------------------<4 DTR     |
|                      | |        | |                             |
|  BATTERY-LOW 5<------------//--------47K--+--47K--+--<7 RTS     |
|                      | |        | |       |       |             |
|                       -          -        |    E  |             |
|    NOTES:                                 |B  |<--+             |
|    RTS must be held at +V SPACE.          +---|                 |
|    TXD must be held at -V MARK.       2N3906  |---+--<1 DCD     |
|    All resistors are 5% 1/8W CF.               C  |             |
|    Cable type is shielded 28AWG.                 4K7            |
|    The DB shells are connected                    |             |
|    to each other via the shield.                  +--<3 TXD     |
|                                                                 |
+-----------------------------------------------------------------+
|                                                                 |
|    Operation:   The UPS communicates with the Computer via      |
|    the RS-232 handshaking lines only, and does not use any      |
|    serial protocol. Upon power fail, the UPS forces CTS to      |
|    -V MARK. When the battery is low, the UPS forces DCD to      |
|    +V SPACE via the transistor. When the Computer forces a      |
|    +V SPACE on DTR, the UPS will shut down and turn off.        |
|    Presence of the cable can be sensed by signaling on TXD      |
|    while monitoring DCD.                                        |
|                                                                 |
+-----------------------------------------------------------------+
|                                                                 |
|                           Male (pins)        Female (holes)     |
|   DB9 RS-232  PC                                                |
|   type connector          1         5         5         1       |
|  ----------------       _______________     _______________     |
|  Pinout numbering       \  . . . . .  /     \  o o o o o  /     |
|  looking into the        \  . . . .  /       \  o o o o  /      |
|  end of the cable         -----------         -----------       |
|                             6     9             9     6         |
|                                                                 |
|  NOTE: Solder a wire to the metal shell for use as a FRAME-GND  |
|                                                                 |
+-----------------------------------------------------------------+
+-----------------------------------------------------------------+
|                                                                 |
|  Gray APC 940-0095A Smart Signalling UPS Cable Wiring Diagram   |
|  This information is verified and tested to be 100% correct.    |
|                                                                 |
+-----------------------------------------------------------------+
|                                                                 |
|      DB9M(UPS)          2m Cable              DB9F(Computer)    |
|      ---------          --------              --------------    |
|                                                                 |
|        (SHELL)<-------+----//----+--------------------<(SHELL)  |
|                       |          |                              |
|      CHASSIS 9<--+    -          -                              |
|                  |   | |        | |                             |
|       COMMON 4<--+---------//-------------------------<5 SG     |
|                      | |        | |                             |
|  BATTERY-LOW 5<------------//--------47K--+--47K--+---<4 DTR    |
|                      | |        | |       |       |             |
|                                           |       +---<6 DSR    |
|                      | |        | |       |    E  |             |
|   NOTES:                                  |B  |<--+---<8 CTS    |
|   DTR must be held at +V SPACE. | |       +---|                 |
|   TXD must be held at -V MARK.         2N3906 |---+---<1 DCD    |
|   All resistors are 5% 1/8W CF. | |            C  |             |
|   Cable type is shielded 28AWG.                  4K7            |
|   The DB shells are connected   | |               |             |
|   to each other via the shield.        +----4K7---+---<3 TXD    |
|                      | |        | |    |                        |
|                                        |                        |
|                      | |        | |    |   1N4148               |
|     SHUTDOWN 1<------------//----------+----|<|-------<7 RTS    |
|                      | |        | |        K   A                |
|   POWER-FAIL 2<------------//---------------------+---<2 RXD    |
|                      | |        | |               |             |
|                       -          -                +---<9 RI     |
|                                                                 |
+-----------------------------------------------------------------+
|                                                                 |
|    Operation:   The UPS can communicate with the Computer       |
|    solely via the RS-232 handshaking lines, or via RS-232       |
|    serial protocol at 2400-8N1 with software flow control.      |
|    Upon power fail, the UPS forces RI to -V MARK. When the      |
|    battery is low, the UPS forces DCD to +V SPACE via the       |
|    transistor. When the Computer forces a +V SPACE on RTS,      |
|    the UPS will shut down and turn off. Jumpered pins in        |
|    the DB9F connector allow for automatic automatic or PNP      |
|    cable identification by UPS software.                        |
|                                                                 |
+-----------------------------------------------------------------+
|                                                                 |
|                           Male (pins)        Female (holes)     |
|   DB9 RS-232  PC                                                |
|   type connector          1         5         5         1       |
|  ----------------       _______________     _______________     |
|  Pinout numbering       \  . . . . .  /     \  o o o o o  /     |
|  looking into the        \  . . . .  /       \  o o o o  /      |
|  end of the cable         -----------         -----------       |
|                             6     9             9     6         |
|                                                                 |
|  NOTE: Solder a wire to the metal shell for use as a FRAME-GND  |
|                                                                 |
+-----------------------------------------------------------------+
+-----------------------------------------------------------------+
|                                                                 |
|  APC 940-1000 Straight Through cable                            |
|  Universal APC serial extension cable for use in conjunction    |
|  with an APC UPS cable. This cable is verified to work.         |
|                                                                 |
+-----------------------------------------------------------------+
|                                                                 |
|  DB9M to UPS cable     Shielded Cable       DB9F to Computer    |
|  -----------------     --- 28AWG ----       ----------------    |
|                                                                 |
|    (SHELL)<----+-------------//-------------+----<(SHELL)       |
|                |                            |                   |
|                -                            -                   |
|               | |                          | |                  |
|          1<------------------//------------------<1 DCD         |
|               | |                          | |                  |
|          2<------------------//------------------<2 RXD         |
|               | |                          | |                  |
|          3<------------------//------------------<3 TXD         |
|               | |                          | |                  |
|          4<------------------//------------------<4 DTR         |
|               | |                          | |                  |
|          5<------------------//------------------<5 SG          |
|               | |                          | |                  |
|          6<------------------//------------------<6 DSR         |
|               | |                          | |                  |
|          7<------------------//------------------<7 RTS         |
|               | |                          | |                  |
|          8<------------------//------------------<8 CTS         |
|               | |                          | |                  |
|          9<------------------//------------------<9 RI          |
|               | |                          | |                  |
|                -                            -                   |
| NOTE: The DB shells are connected to each other via the shield. |
|                                                                 |
+-----------------------------------------------------------------+
|                                                                 |
|                           Male (pins)        Female (holes)     |
|   DB9 RS-232  PC                                                |
|   type connector          1         5         5         1       |
|  ----------------       _______________     _______________     |
|  Pinout numbering       \  . . . . .  /     \  o o o o o  /     |
|  looking into the        \  . . . .  /       \  o o o o  /      |
|  end of the cable         -----------         -----------       |
|                             6     9             9     6         |
|                                                                 |
|  NOTE: Solder a wire to the metal shell for use as a FRAME-GND  |
|                                                                 |
+-----------------------------------------------------------------+

GE, IMV and Victron cable reference

Desc: IMV Victron UPS cables
File: victron.txt
Date: 13 April 2002
Auth: Daniel Prynych <Daniel.Prynych@hornet.cz>

Data cable 1 for UPS:
  GE/IMV/Victron Match - 500 700 700L 1000 1000L 1500 2200 3000
  GE/IMV/Victron NetPro (NetPro 19 ") - 600 1000 1200 2000 3000 4000

Driver: victronups (newvictronups)


UPS         PC  9 pin connector
1 --------- 3
2 --------- 2
5 --------- 5 GND
            4 DTR
            |
            1 DCD

------------------------------------

Data cable 2 for UPS:
   GE/IMV Victron Match Lite (all types)


Driver: victronups (newvictronups)

UPS         PC  9 pin  connector
2 --------- 3
3 --------- 2
4 --------- 5 GND
            4 DTR
            |
            1 DCD

-----------------------------------
Crack cable: for UPS

  Victron Lite (no IMV Victron Match Lite)


Driver: genericups

UPS          PC 9 pin connector
1 ---------- 4 DTR
7 ---------- 1 DCD ----------+
9 ---------- 8 CTS -----+    |
5 ---------- 5 GND      |    |
                        |    |
                        R    R 6,8k - 10k ohm
                        |    |
             7 RTS------+----+

----------------------------------------------
GE is General Electric Company.

On July 31, 2001, the General Electric Company, acquired IMV (Victron) company.

IMV Match19 cable reference

Desc: IMV Match19 700 - 1500
File: imv.txt
Date: 06 April 2002
Auth: Niels S. Richthof <niels@richthof.de>


"UPS-VIC23-2"        PC 9 pin connector

  1 ---------------- 3
  2 ---------------- 2
  4 ---------------- 7
  5 ---------------- 5

MGE UPS SYSTEMS serial cable reference

Desc: MGE UPS SYSTEMS serial cable
File: mgeups.txt
Date: 10 April 2002
Auth: Arnaud Quette <arnaud.quette@free.fr> or <arnaud.quette@mgeups.com>

This document describes the cable for MGE smart protocols : UTalk (ASCII),
and SHUT (Serial HID UPS Transfer, binary) .

First notice that MGE UPS SYSTEMS supply a standard cable, bundled with
the UPS unit and compatible with MS Windows and Unices (Ref 66049). For
more information, see below note about serial cable, PnP and Unix.

Cable description
-----------------

UPS                  COMPUTER
MALE DB9             FEMALE DB9

  2 ---------------- 2 TX
  3 ---------------- 3 RX
  5 ---------------- 5 GND
                  -- 4
                 |
                  -- 6
                  -- 7
                 |
                  -- 8


UPS connector description
-------------------------

       5  4  3  2  1
      _______________
      \o  o  o  o  o/
       \ o  o  o  o/
         ---------
         9  8  7  6

  9 pin Male DB-9 connector on UPS


Notes
-----
        - this is a universal serial cable, so it should work with
        any MGE serial model.
        - max. length of cable is 1,80 m.
        - Computer pin 6 (RTS) is reserved for PnP use, which could
        trouble communication on some Unices if cabled. However, new
        models (such as Ellipse, Evolution, Pulsar and Comet EXtreme,
        EXtreme C, ...) handle this, so you can safely cable pin 6 or
        use a standard (bundled) "windows" cable (Ref 66049).

Powerware cable reference

Desc: Powerware 3115 factory cable
File: powerware.txt
Date: 22 July 2005
Auth: various

1) Powerware 3115 factory cable
From Peter Åstrand <altic@lysator.liu.se>

UPS         PC  9 pin connector
5 --------- 1
2 --------- 2
1 --------- 3
4 --------- 5
6 --------- 8

2) Powerware 5119 RM Cable Layout
From Daniel Thompson <danht@callthenet.com>

UPS <-----------> PC
DB9-M <--------> DB9-F
Pin 1 <-----------> Pin 3
Pin 2 <-----------> Pin 8
Pin 4 <-----------> Pin 4
Pin 5 <-----------> Pin 1
Shells Grounded Both Ends

Repotec cable reference

Desc: Repotec 800A (800VA) & 162A (1600VA) cable
File: repotec.txt
Date: 11 April 2001
Auth: Theodor Milkov <zimage@delbg.com>


PC                      UPS

1 (DCD) <----+---------- 2
             |
             R 5.6k
             |
7 (RTS) >----+

3 (Tx)  >--------------- 6

4 (DTR) <----+---------- 5
             |
             R 5.6k
             |
8 (CTS) >----+

5 (GND) -------------+-- 4
                     |
                     +-- 7

SMS cable reference

Desc: SMS UPS cables, for Upsilon compatible SMS UPS
File: sms.txt
Date: 9 October 2001
Auth: Marcio Gomes <tecnica@microlink.com.br>


COMPUTER        UPS
FEMEA DB9      MACHO DB9
2    ----------  6
3    ----------  9
4/8  ----------  5
5    ----------  8

- This cable is working with Manager III 1300 VA and 650 VA, SMS UPS's
- Jump in computer side pins 4/8 and connect to pin 1 in UPS side
- Use NUT blazer_ser driver