  • All values are stored as U16

  • Gain: the value read out must divide this value

  • Type: the data type AFTER applying the gain

  • Example:

    • Voltage reading from the register is 2262

    • Gain is 10

    • Type is Real

    • ⇒ actual Voltage = 226.2

  • All register address may add UPS ID multiplied by 10000. However when using on-device serial port, the UPS ID is 1 fixed. Querying only with register address without the UPS ID also works when there is only one device.

    • e.g. Address of Input Voltage register is 1000

    • UPS ID is 1

    • ⇒ Register ID used to send request is 11000 (0x2AF8), or 1000 (0x03E8)

  • All reserved bits in bit flags shall be 0 unless noticed otherwise.

Name

Gain

Type

Unit / Range

Address

Length (in U16)

R/W

Input Voltage

10

Float

V

1000

1

R

Input Frequency

10

Float

Hz

1003

1

R

Bypass Voltage

10

Float

V

1004

1

R

Bypass Frequency

10

Float

Hz

1007

1

R

Output Voltage

10

Float

V

1008

1

R

Output Current

10

Float

A

1011

1

R

Output Frequency

10

Float

Hz

1014

1

R

Output Active Power

10

Float

kW

1015

1

R

Output Apparent Power

10

Float

kVA

1018

1

R

Output Load Percentage

10

Float

%

1021

1

R

Output Route State

1

Enum

0=No Power
1=On Bypass
2=On Mains
3=On Battery
5=On Mains ECO

1024

1

R

Input Method

1

Enum

0=Single Phase

1025

1

R

Output Method

1

Enum

0=Single Phase

1026

1

R

Temperature

10

Float

1027

1

R

UPS Status

1

Bit Flag

Bit 7=Mains Abnormal (0=Normal/OL 1=Abnormal/OB)

Bit 6=Low Battery (0=Normal 1=Low/LB)

Bit 5=Reserved

Bit 4=Internal Error (0=Normal 1=Error)

Bit 3=UPS Type (0=Offline/Backup 1=Online/Double Conversion)

Bit 2=Battery Self-Checking (0=Not checking 1=Self checking)

Bit 1=Reserved

Bit 0=Reserved

Other Bits=Reserved

1043

1

R

Battery Voltage

10

Float

V

2000

1

R

Battery Status

1

Enum

2=Sleeping
3=Trickle Charging
4=Balanced Charging
5=Discharging

2002

1

R

Battery Remaining Capacity

1

U16

%

2003

1

R

Battery Estimated Remaining Time

1

U32

Seconds

2004

2

R

Battery Cells

1

U16

Cells

2007

1

R

Battery Capacity

1

U16

Ah

2033

1

R

UPS Rated Power

10

Float

kVA

9009

1

R

Controlling Registers

Note
  • Type Bool means write 0 to disable the function and write 1 to enable unless noticed otherwise.

  • Type Exec means write 1 to execute the function unless noticed otherwise.

Name

Gain

Type

Unit / Range

Address

Length (in U16)

R/W

Startup State

1

Enum

0=Powered Off (Can be turned on)
1=Powering On (processing, front control panel is blocked)
2=Power On Failed (Can be turned on)
3=Powered On (Can be turned off)

1028

1

R

Power On

1

Exec

1029

1

W

Power Off

1

Exec

1030

1

W

ECO Mode

1

Bool

1030

1

W

Auto Power On After Mains Attached

1

Bool

1044

1

R/W

Bypass Output

1

Bool

1045

1

R/W

Mute Buzzer

1

Bool

1046

1

R/W

Delayed Restart (By 0.1 minutes)

10

Float

0.1 minutes (0.1min ~ 99.0min)

1047

1

R/W

Delayed Restart (By 1 minutes)

1

U16

1 minutes (1min ~ 9999min)

1048

1

R/W

Delayed Power Off (By 0.1 minutes)

10

Float

0.1 minutes (0.1min ~ 99.0min)

1049

1

R/W

Cancel Delayed Powered Off

1

Exec

1050

1

W

Deep Battery Self Check (Until Low Battery)

1

Exec

2021

1

W

End Battery Self Check

1

Exec

2023

1

W

Shallow Battery Self Check

1

Exec

2028

1

W