Network UPS Tools
Power Devices support
Table of Contents

Click here to see reports of other supported models from Cyber Power Systems.

Note

When a user reports that a variable/command is not right then it will be highlighted by a red underline.

Bad values/ranges/etc… will get a red dashed outline or red solid left border.

The accompanying explaining comment - if provided - will be emphasized through a red dotted border on the left.

2.7.2

Report #1 with driver usbhid-ups (detailed comments available)

This device is known to work with driver usbhid-ups.

You can grab a dummy-ups compliant .dev file to simulate this device clicking here.

Some more detailed comments are available after the "Known supported…" sections.

Known supported variables

This device is known to support the following variables (values are just examples):

battery.charge

100

battery.charge.low

10

battery.charge.warning

20

battery.mfr.date

CPS

battery.runtime

3012

battery.runtime.low

300

battery.type

PbAcid

battery.voltage

17.7

To the value is applied a 0.667 scale that’s not needed; fixed in newer versions of NUT.

battery.voltage.nominal

24

device.mfr

CPS

device.model

Value1200E

device.type

ups

driver.name

usbhid-ups

driver.parameter.offdelay

20

driver.parameter.ondelay

1

driver.parameter.pollfreq

30

driver.parameter.pollinterval

2

driver.parameter.port

auto

driver.version

2.7.2

driver.version.data

CyberPower HID 0.3

driver.version.internal

0.38

input.transfer.high

0

input.transfer.low

0

input.voltage

235.0

input.voltage.nominal

230

output.voltage

239.0

ups.beeper.status

enabled

ups.delay.shutdown

20

ups.delay.start

1

ups.load

11

ups.mfr

CPS

ups.model

Value1200E

ups.productid

0501

ups.realpower.nominal

720

ups.status

OL

ups.test.result

No test initiated

ups.timer.shutdown

-60

ups.timer.start

-60

ups.vendorid

0764